RTU-MP Controller
19
Demand Limiting
If the RTU-MP receives a level
1
(one degree offset),
2
(two degree offset), or a
3
(4 degree offset) to the
BACnet demand limit variable, the controller expands the heating and cooling setpoints by the configured
demand limit setpoint value and remain in effect until the BACnet demand limit variable receives a
0
value.