58
SV01
— Condenser Solenoid Valve
SV02
— Compressor Solenoid Valve
SV03
— Pumpout Solenoid Valve
SV04
— Drain Solenoid Valve
SV05
— Regeneration Solenoid Valve
SV06
— Vent Solenoid Valve
TS01
— Purge Compressor Inlet Temperature
Fig 30
– Purge system wiring
3TR
— Transformer
4TR
— Transformer
7TB 1,2
— 24VAC Low Voltage Wiring Terminal Block
7TB LL1, LL2
— Main One Phase Power
7TB PE
— Ground
CC
— Purge Compressor/Fan Contactor
HC
— Purge Heater Contactor
HSR
— High Level Switch Relay
LSR
— Low Level Switch Relay
PR
— Purge Vacuum Pump Relay
SIOB
— Purge Input/Output Board
Fig 31
– Purge system control box
3.6.3 High pressure safety accessory: SRMCR
– Chiller equipped with VFD LF2
3.6.3.1 General description :
The unit is equipped with a safety loop, also called measurement, control and regulation devices playing a role in
safety (SRMCR for protection against overpressure that could be created by the compressor).
Made of :
-
2 active pressure switches (HPS) at compressor discharge
-
Safety relay K4 inside the control cabinet
-
Power contactor K101 inside the LF2 VFD
-
LF2 VFD
See chiller wiring diagram and bill of material (part numbers).
This SRMCR is designed in accordance with EN ISO 13849-1: 2016 according to the following characteristics:
- PL d
- Category 3.
Содержание PIC 5+
Страница 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Страница 52: ...52 Fig 24 19DV control box ...
Страница 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Страница 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Страница 57: ...57 ...
Страница 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Страница 114: ...114 Detailed menu description ...
Страница 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...