29
(VFD not shown
)
Fig 13
– Sensors, actuators location (end)
2.6.4 Temperature sensors:
The system uses temperature sensors to measure and control the temperatures in the unit. There are three types
of temperature sensors, 5K thermistor (standard), 10K thermistor and RTD (three wires) based on the IOB
channel configurations.
Wiring information (see chiller wiring diagram)
Temperature sensor
Point Name
Designation
#IOB
# Channel
# Block
# Terminal
Entering chilled water temperature
ECW
RT1
IOB 1
AI1
J16
1-5
Leaving chilled water temperature
LCW
RT2
IOB 1
AI2
J16
2-6
Entering condenser water temperature
ECDW
RT7
IOB 1
AI3
J16
3-7
Leaving condenser water temperature
LCDW
RT8
IOB 1
AI4
J16
4-8
Evap. refrigerant liquid temperature
EVAP_T
RT15
IOB 1
AI5
J15
6-12
Compressor Discharge temperature
DGT
RT21
IOB 1
AI6
J15
5-11
Motor winding temperature 1
MTRW1
RT31C
IOB 2
AI1
J16
1-5
1st stage Bearing Temp
CBH1_T
RT39C
IOB 3
AI1
J16
1-5
2nd stage Bearing temp
CBH2_T
RT40C
IOB 3
AI2
J16
2-6
Bearing Ref Supply Temp
BRGI_T
RT41
IOB 3
AI3
J16
3-7
The temperature sensor range is -40 ~ +118°C.
Table 1a
– Temperature sensors
Содержание PIC 5+
Страница 26: ...26 VFD not shown Fig 13 Sensors actuators location ...
Страница 52: ...52 Fig 24 19DV control box ...
Страница 53: ...53 1 Power supply 24V AC 2 LEN 3 CCN 4 Ethernet 5 USB Fig 25 19DV HMI box rear view ...
Страница 54: ...54 Fig 26 19DV IOB1 wiring Fig 27 19DV IOB2 wiring ...
Страница 57: ...57 ...
Страница 113: ...113 APPENDIX A SmartView SCREEN AND MENU STRUCTURE ...
Страница 114: ...114 Detailed menu description ...
Страница 116: ...116 APPENDIX B MAINTENANCE SUMMARY AND LOGSHEETS Cont 19DV monthly Maintenance Log ...