
9
WATER PIPING
Supply and return piping must be as large as the unit connections
on the heat pump (larger on long runs).
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper
equipment operation.
Never use flexible hoses of a smaller inside diameter than
that of the fluid connections on the unit.
GZ units are supplied with either a copper or optional cupronickel
water coax coil. Copper is adequate for ground water that is not
high in mineral content.
NOTE
: Proper testing is recommended to assure the well water
quality is suitable for use with water source equipment. When in
doubt, use cupronickel. See Application Considerations notes on
page 4.
In conditions anticipating moderate scale formation or in brackish
water, a cupronickel heat exchanger is recommended.
Both the supply and discharge water lines will sweat if subjected to
low water temperature. These lines should be insulated to prevent
damage from condensation. All manual flow valves used in the
system must be ball valves. Globe and gate valves must not be
used due to high pressure drop and poor throttling characteristics.
CAUTION
!
EQUIPMENT
DAMAGE
AND/OR
UNIT
OPERATION HAZARD
Failure to follow this caution may result in equipment
damage and/or improper operation.
Never exceed the recommended water flow rates as serious
damage or erosion of the water--to--refrigerant heat
exchanger could occur.
Always check carefully for water leaks and repair appropriately.
Units are equipped with female pipe thread fittings.
NOTE
: Teflon tape sealer should be used when connecting water
piping connections to the units to insure against leaks and possible
heat exchanger fouling.
NOTE
: The unit is shipped with water connection O--rings. A 10
pack of O--rings (part #4026) can be ordered through Replacement
Components Division (RCD).
IMPORTANT: Do not over--tighten connections.
Flexible hoses should be used between the unit and the rigid
system to avoid possible vibration. Ball valves should be installed
in the supply and return lines for unit isolation and unit water flow
balancing (on open--loop systems).
Loop Pump Connections
Refer to the flow center installation manual for piping and wiring
instructions.
When using a flow center containing a variable speed pump, kit
#4129 is required.
Water Solenoid Valves
Open loop well water applications require a water solenoid valve.
The purpose of the valve is to allow water to flow through the
GHP only during operation.
For ground water/open loop installations, solenoid valves
MVBR3F and MVBR4F are recommended due to its fast
opening/slow closing timing feature (see Fig. 7). This valve will
open in approximately 5 seconds. Solenoid valves that are slow
opening are not recommended as water in the unit’s coax may
freeze during start--up of a heating call. A frozen coax is not
covered under warranty. MVBR3 and MVBR4F valves are also
slow closing to eliminate potential water hammer.
Information on the MVBR3F and MVBR4F valves is shown
below.
A150629
Fig. 7 -- Solenoid Valves
Table 7 – Water Solenoid Valves
Part Number
Description
MVBR3F
Valve, motorized solenoid, forged brass ¾“ FPT, 24V
MVBR3F
Valve, motorized solenoid, forged brass 1” FPT, 24V
Flow Regulator Valves
A flow regulator valve should be used in open loop / well water
applications to set the flow rate through the heat pump. The lowest
entering fluid temperature (EWT) expected should be used to
determine the flow rate per ton. 1.5 GPM per ton is acceptable for
50
_
F (10
_
C) EWT or higher. 2 GPM per ton should be used if
EWT is below 50
_
F (10
_
C). (See Fig. 8 and Table 8)
A150630
Fig. 8 -- Flow Regulator
Table 8 – Flow Regulators
Part Number
Flow Regulator Valves
FR2
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 2 GPM
FR3
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 3 GPM
FR4
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 4 GPM
FR5
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 5 GPM
FR6
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 6 GPM
FR7
Valve, flow regulator, 3/4” FPT x 3/4” FPT, 7 GPM