TROUBLESHOOTING UNITS FOR PROPER

SWITCHING BETWEEN LOW & HIGH

STAGES

Check the suction pressures at the service valves. Suction pressure

should be reduced by 3--10% when switching from low to high

capacity.
Compressor current should increase 20 to 45% when switching

from low to high stage. The compressor solenoid when energized

in high stage, should measure 24VAC across pin numbers PL5--2

HI and PL5--5 C . When the compressor is operating in low stage,

the 24V DC compressor solenoid coil is de--energized. When the

compressor is operating in high stage, the 24V DC solenoid coil is

energized.
The solenoid plug harness that is connected to the compressor has

an internal rectifier that converts the 24V AC signal to 24V DC.

DO NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER

.

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by

the DC solenoid, that modulates between high and low stage. If it

is suspected that the unloader is not working, the following

methods may be used to verify operation.

1. Operate the system and measure compressor amperage. Cy-

cle the unloader on and off at 30 second plus intervals at the

User Interface (from low to high stage and back to low

stage). Wait 5 seconds after staging to high before taking a

reading. The compressor amperage should go up or down

at least 20 percent.

2. If the expected result is not achieved, remove the solenoid

plug from the compressor and with the unit running and the

User Interface or thermostat calling for high stage, test the

voltage output at the plug with a DC voltmeter. The read-

ing should be 24 volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance. The

resistance should be approximately 330 or 1640 ohms de-

pending on unloader coil supplier. If the coil resistance is

infinite or is grounded, the compressor must be replaced.

Two Stage Compressor

The two stage compressor contains motor windings that provide

2--pole (3500 RPM) operation.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into the compressor shell when

differential between suction and discharge pressure exceeds

550--625 psi. The compressor is also protected by an internal

overload attached to motor windings.

Compressor Control Contactor

The contactor has a 24volt coil. The electronic control board

controls the operation of the contactor.

Troubleshoot Compressor

If the compressor fails to operate, Table 16 can be used to verify if

there is any damage to the compressor windings causing system

malfunction.

Table 16 – Winding Resistance

Compressor Ohms

Model

Start Winding

Run Winding

GZ024

1.64

1.3

GZ036

1.52

0.88

GZ048

1.86

0.52

GZ060

1.63

0.39

GZ072 1.85

0.34

Tol/- 7%. All resistance values must be measured with

compressor at room temperature.

Systems Communication Failure

If communication with the compressor control is lost with the
Communicating System Wall Control, the control will flash the

appropriate fault code (see Table 15) to the rest of the

communicating system, including the wall control and the indoor
split geothermal unit.

Model Plug

Each control board contains a model plug. The model plug is used
to identify the type and size of unit to the control.
The correct model plug must be installed for the system to operate

properly (see Table 17).

Table 17 – Model Plug Information

Model

Model Plug

Number

Pins 1---4

Pins 2---3

GZ024

HK70EZ001

5.1K

11K

GZ036

HK70EZ002

5.1K

18K

GZ048

HK70EZ003

5.1K

24K

GZ060

HK70EZ004

5.1K

33K

GZ072

HK70EZ005

5.1K

39K

On new units, the model and serial numbers are input into the
board’s memory at the factory. If a model plug is lost or missing at

initial installation, the unit will operate according to the
information input at the factory and the appropriate error code will

flash temporarily.

NOTE

: RCD replacement boards contain no model and serial

information. If the factory control board fails, the model plug must
be transferred from the original board to the replacement board for
the unit to operate.

NOTE

:

The model plug takes priority over factory model

information input at the factory. If the model plug is removed after
initial power up, the unit will operate according to the last valid
model plug installed, and flash the appropriate fault code
temporarily.

Troubleshooting the Model Plug

If the unit is being identified incorrectly by model or size, verify
the plug resistance per Table 17. If resistance value verifies the

plug is good, ensure the plug is dry and condensate free.

NOTE

: Dielectric grease (field supplied) can be used on model

plug pins if condensate has been noted after drying the plug.

Содержание GZ024

Страница 1: ...ualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this prod...

Страница 2: ...laims with the carrier Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt Location Clearance To maximize syst...

Страница 3: ...ons See Fig 3 Diagram shows typical vertical package unit installation and is for illustration purposes only Ensure access to Heat Pump is not restricted Note Package unit shown GZ unit is connected t...

Страница 4: ...ll to supply both domestic water and the heat pump care must be taken to insure that the well can provide sufficient flow for both In well water applications a slow closing solenoid valve must be used...

Страница 5: ...will occur Corrosion Prevention pH All 6 8 5 Monitor treat as needed 6 8 5 Minimize steel pipe below 7 and no open tanks with pH 8 Hydrogen Sulfide H2S All At H S 0 2 ppm avoid use of copper and coppe...

Страница 6: ...INSTALLATIONS Power Disconnects Air Handler Vibration Isolator Pad Fig 5 Typical Split with Air Handler Installation Vibration Isolator Pad Power Disconnects Fig 6 Typical Split with A coil Furnace In...

Страница 7: ...liquid lines affects system performance to a lesser degree provided that a solid column of liquid no flash gas is being delivered to the refrigerant metering device and that the liquid pressure at the...

Страница 8: ...tem charge Factory charge 45 ft 25 ft X 60 oz ft Total system charge 86 oz 20 ft x 60 oz ft 98 oz Additional 12 oz of R410A refrigerant required Model GZ060 with 10 ft of equivalent length of 3 8 O D...

Страница 9: ...e hoses should be used between the unit and the rigid system to avoid possible vibration Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing...

Страница 10: ...s 3 tons and smaller one valve is typical For larger two stage heat pumps there is an opportunity to save a significant amount of energy and avoid wasting water with the use of two solenoid valves one...

Страница 11: ...r piping allowing all air to bleed out until water appears at valve 6 Before restoring the power or fuel supply to the water heater adjust the temperature setting on the tank thermostat s to ensure ma...

Страница 12: ...by a pause then 7 long flashes followed by another pause and repeats this series The Wall Control will display text on the screen for the last 10 events S Exit service screens by selecting Done Non Co...

Страница 13: ...ber that all sides of the cabinet are accessible but in event the unit is placed where all sides make this difficult removal of the box may help The transformer is a 75va transformer which should prov...

Страница 14: ...IMPORTANT A160124 Communicating controls notes 1 Y2 connector ST1 is used for a utility curtailment input and is not available for use as an output for the second valve However the wiring harness exte...

Страница 15: ...esult in unit damage and or improper equipment operation If heat recovery unit is installed in an area where freezing may occur the unit must be drained during winter months to prevent heat exchanger...

Страница 16: ...ws the UI to display outdoor air temperature A150195 Fig 20 OAT Sensor Connection Compressor Start Accessories In the event of the rare occurrence of compressor starting issues such as dimming of the...

Страница 17: ...aries are dual tapped for 208 and 230 volts Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage 24 volts is ideal for best operation jThe following guidelines are rec...

Страница 18: ...access the refrigerant system at start up on package units Access should only be necessary as last resort in troubleshooting to prevent unnecessary charge issues j Check the water flow and operating...

Страница 19: ...SEC YES NO NO YES START ANTI SHORT CYCLE INITIAL POWER UP YES NO START RANDOM START UP START COUNTER NEEDED YES COUNT 2 OR COUNT 4 BLINK CODE ON STATUS LED DISPLAY OUTPUT PULSE ALR OUTPUT ON PULSE NO...

Страница 20: ...ducing the effective displacement of the compressor Full capacity is achieved by blocking these vents thus increasing the displacement to 100 A DC solenoid in the compressor controlled by a rectified...

Страница 21: ...mportant to have the Freeze1 set to the default 26_F 3 33_C CAUTION UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in unit damage and or improper equipment operation Fre...

Страница 22: ...temperature would be set too high then the GHP would not be providing the customer with the best efficiency due to extended operation run hours of the gas furnace or electric heat resulting in higher...

Страница 23: ...M 1064 1063 QUIET N A 911 048 Low 936 Max 1486 1486 EFF 1 1207 1207 EFF 2 1300 1300 COM 1107 1105 QUIET N A 947 048 High 1080 Max 1714 1714 EFF 1 1393 1393 EFF 2 1500 1500 COM 1277 1275 QUIET N A 1093...

Страница 24: ...1 1 1 0 1 0 10 2 3 2 2 2 0 2 0 1 9 1 8 1 8 1 7 1 7 15 4 8 4 7 4 2 4 1 3 9 3 8 3 7 3 6 3 5 GZ072 9 1 0 1 0 0 9 0 9 0 9 0 8 0 8 0 8 0 8 12 1 7 1 7 1 5 1 5 1 4 1 4 1 3 1 3 1 3 18 3 6 3 5 3 2 3 1 3 0 2 9...

Страница 25: ...Load 30 4 76 92 242 297 3 4 13 14 8 80 97 249 304 2 3 13 15 40 4 125 151 180 221 14 18 19 22 89 108 255 312 4 5 15 17 8 120 146 169 207 8 10 20 23 93 113 261 320 3 3 16 18 50 4 134 163 211 258 14 18...

Страница 26: ...4 5 74 90 244 299 3 4 13 15 9 0 78 95 251 306 2 3 13 16 40 4 5 122 149 183 224 14 18 19 23 87 106 257 314 4 5 15 18 9 0 117 143 172 210 8 10 20 24 91 111 263 322 3 3 16 19 50 4 5 131 160 214 261 14 1...

Страница 27: ...1 87 277 339 6 7 15 19 12 0 75 92 284 347 4 5 16 20 40 6 0 118 144 194 237 21 25 19 23 84 102 291 356 7 9 18 22 12 0 113 138 182 223 12 14 20 24 88 108 299 365 5 6 19 23 50 6 0 127 155 226 276 21 25 1...

Страница 28: ...7 0 68 84 256 313 5 7 19 23 14 0 73 89 261 319 4 5 20 25 40 7 0 117 143 182 222 15 19 21 26 81 99 277 339 7 8 22 26 14 0 114 139 170 208 11 14 22 27 86 105 283 346 5 6 23 28 50 7 0 120 147 215 263 15...

Страница 29: ...9 0 71 87 259 316 5 7 19 23 18 0 76 92 264 322 4 5 20 25 40 9 0 120 146 185 225 15 19 21 26 84 102 280 342 7 8 22 26 18 0 117 142 173 211 11 14 22 27 89 108 286 349 5 6 23 28 50 9 0 123 150 218 266 1...

Страница 30: ...eeze Sensor Fault 57 Freeze sensor is invalid or out of range Check for open sensor wire disconnected sensor not connect ed properly or abnormal sensor temp ranges Compressor Thermal Cutout in Low Sta...

Страница 31: ...pressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24volt coil The electronic control board controls the operation of the con...

Страница 32: ...ntrol of the system In this manner the service technician can run the diagnostic checkouts right at the outdoor unit using the service tool After the checkouts are completed and it is no longer necess...

Страница 33: ...00 11 52 18 970 57 135 2 774 103 217 622 34 29 227 600 12 54 18 090 58 136 2 674 104 219 604 33 27 213 600 13 55 17 260 59 138 2 579 105 221 587 32 26 200 500 14 57 16 470 60 140 2 488 106 223 571 31...

Страница 34: ...of the unit is a normal protective measure in the design of the equipment If continual lockouts occur call a mechanic immediately and have them check for the following Water flow problems Water tempe...

Отзывы: