background image

17

PRE START--UP CHECKLIST

CAUTION

!

UNIT DAMAGE AND/OR OPERATION HAZARD

Failure to follow this caution may result in unit damage

and/or improper equipment operation.
Equipment should never be used during construction due

to likelihood of wall board dust accumulation in the air

coil of the equipment which permanently affects the

performance and may shorten the life of the equipment.

CAUTION

!

UNIT DAMAGE AND/OR OPERATION HAZARD

Failure to follow this caution may result in unit damage

and/or improper equipment operation.
Check with all code authorities on requirements involving

condensate disposal/overflow protection criteria.

j

Ensure the isolation valves are open and water control valves are

wired.

j

Loop/water piping is complete and flushed, (clean and purged of

air).

j

Verify loop water chemistry meets requirements on water

chemistry table (reference table 1)

j

Antifreeze is added if necessary

j

Verify HRP switch is energized, if applicable. Recommend

de--energize if installed and water not available.

j

Verify the HRP system is purged and connected completely, if

applicable.

j

Verify the freeze protection is set according to proper freeze

temperature (26 or 15

_

F)

j

Remove access panels to access applicable compartments.

j

Verify sufficient space is available for accessing and servicing

areas such as the blower and electric heat compartment and the

compressor and electrical control box compartment.

j

Verify all supply voltage is in accordance with unit nameplate.

j

Verify all wiring is tight and secure.

j

Check that the unit blower is free to rotate and wheel is secure to

shaft.

j

Verify the condensate drain pan is clear and drains with proper

external trap and pipe pitch.

j

Ensure the system air filters are installed.

j

Ensure no wiring is pinched when panels are re--installed.

j

Verify loop pump wiring, if applicable, is in accordance with the

pump installation instructions.

j

Verify all system accessories and components are wired per

applicable instructions and all wiring in accordance with NEC.

j

If non--communicating thermostat ensure the UPM dip switch

settings are configured accordingly for Freeze Protection,

Lockout trip setting and Brownout). UPM dip switch settings

can be configured in the User Interface during set up (see steps

below in user interface quick setup).

j

Ensure all panels are in place before powering up the unit.

j

Always check incoming line voltage, power supply and

secondary control voltage for adequacy. Transformer primaries

are dual tapped for 208 and 230 volts. Connect the appropriate

tap to ensure a minimum of 18 volts secondary control voltage.

24 volts is ideal for best operation.

j

The following guidelines are recommended for wiring between a

thermostat and the unit: 18 GA up to 60 ft (18.3m), 16 GA up to

100 ft. (30.5m), and 14 GA up to 140 ft. (42.7m).

UNIT START--UP

If the unit utilizes the Communicating User Interface, reference
information in the User Interface Quick Setup section.
Non--communicating thermostats:

j

Set the thermostat to the highest setting.

j

Set the thermostat system switch to “COOL”, and the fan switch

to the “AUTO” position. The reversing valve solenoid should

energize. The compressor and fan should not run.

j

Reduce the thermostat setting approximately 5 degrees below

room temperature.

j

Verify the heat of rejection is within 10% of the product data for

conditions the unit is started under in cooling mode.

j

Turn the thermostat system switch to the “OFF” position. The unit

should stop running and the reversing valve should de--energize.

j

Leave the unit off for approximately five (5) minutes to allow for

system equalization.

j

Turn the thermostat to the lowest setting.

j

Set the thermostat switch to “HEAT”.

j

Increase the thermostat setting approximately five (5) degrees

above room temperature.

j

Verify the unit heat of extraction is within 10% of the unit product

data information when started in the heating mode of operation.

j

Set the thermostat to maintain desired space temperature.

j

Check for vibrations, leaks, etc.

j

It is suggested that a start up / commissioning form be completed

for each new installation. This document should be kept at both

the job site and with the project folder of the installing contractor

if needed to refer back to.

USER INTERFACE QUICK SET--UP

Install only approved thermostats per the unit Product Data.

Communicating geothermal units require UI software version 13 or
later. Read and Understand the thermostat Installation Instructions,

this start--up is not intended to replace the thermostat Installation
Instructions.
Install each component per unit Installation Instruction. Wire each

accordingly.
Enter the service and installation screens in the UI
Upon powering up the system, the user interface installation will
seek out the control boards in the unit and recognize the unit model

and size and communicating electric heat, if installed.
Component search order:

S

Indoor (ECM is the indoor if GC model)

S

Outdoor (UPM)

S

SAM if applicable

S

Zoning if applicable

S

Any non--com components via selectable screens.

Run set up to select specific features desired such as UPM switch

settings (brownout, lockout and freeze protection).

Содержание GZ024

Страница 1: ...ualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this prod...

Страница 2: ...laims with the carrier Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt Location Clearance To maximize syst...

Страница 3: ...ons See Fig 3 Diagram shows typical vertical package unit installation and is for illustration purposes only Ensure access to Heat Pump is not restricted Note Package unit shown GZ unit is connected t...

Страница 4: ...ll to supply both domestic water and the heat pump care must be taken to insure that the well can provide sufficient flow for both In well water applications a slow closing solenoid valve must be used...

Страница 5: ...will occur Corrosion Prevention pH All 6 8 5 Monitor treat as needed 6 8 5 Minimize steel pipe below 7 and no open tanks with pH 8 Hydrogen Sulfide H2S All At H S 0 2 ppm avoid use of copper and coppe...

Страница 6: ...INSTALLATIONS Power Disconnects Air Handler Vibration Isolator Pad Fig 5 Typical Split with Air Handler Installation Vibration Isolator Pad Power Disconnects Fig 6 Typical Split with A coil Furnace In...

Страница 7: ...liquid lines affects system performance to a lesser degree provided that a solid column of liquid no flash gas is being delivered to the refrigerant metering device and that the liquid pressure at the...

Страница 8: ...tem charge Factory charge 45 ft 25 ft X 60 oz ft Total system charge 86 oz 20 ft x 60 oz ft 98 oz Additional 12 oz of R410A refrigerant required Model GZ060 with 10 ft of equivalent length of 3 8 O D...

Страница 9: ...e hoses should be used between the unit and the rigid system to avoid possible vibration Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing...

Страница 10: ...s 3 tons and smaller one valve is typical For larger two stage heat pumps there is an opportunity to save a significant amount of energy and avoid wasting water with the use of two solenoid valves one...

Страница 11: ...r piping allowing all air to bleed out until water appears at valve 6 Before restoring the power or fuel supply to the water heater adjust the temperature setting on the tank thermostat s to ensure ma...

Страница 12: ...by a pause then 7 long flashes followed by another pause and repeats this series The Wall Control will display text on the screen for the last 10 events S Exit service screens by selecting Done Non Co...

Страница 13: ...ber that all sides of the cabinet are accessible but in event the unit is placed where all sides make this difficult removal of the box may help The transformer is a 75va transformer which should prov...

Страница 14: ...IMPORTANT A160124 Communicating controls notes 1 Y2 connector ST1 is used for a utility curtailment input and is not available for use as an output for the second valve However the wiring harness exte...

Страница 15: ...esult in unit damage and or improper equipment operation If heat recovery unit is installed in an area where freezing may occur the unit must be drained during winter months to prevent heat exchanger...

Страница 16: ...ws the UI to display outdoor air temperature A150195 Fig 20 OAT Sensor Connection Compressor Start Accessories In the event of the rare occurrence of compressor starting issues such as dimming of the...

Страница 17: ...aries are dual tapped for 208 and 230 volts Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage 24 volts is ideal for best operation jThe following guidelines are rec...

Страница 18: ...access the refrigerant system at start up on package units Access should only be necessary as last resort in troubleshooting to prevent unnecessary charge issues j Check the water flow and operating...

Страница 19: ...SEC YES NO NO YES START ANTI SHORT CYCLE INITIAL POWER UP YES NO START RANDOM START UP START COUNTER NEEDED YES COUNT 2 OR COUNT 4 BLINK CODE ON STATUS LED DISPLAY OUTPUT PULSE ALR OUTPUT ON PULSE NO...

Страница 20: ...ducing the effective displacement of the compressor Full capacity is achieved by blocking these vents thus increasing the displacement to 100 A DC solenoid in the compressor controlled by a rectified...

Страница 21: ...mportant to have the Freeze1 set to the default 26_F 3 33_C CAUTION UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in unit damage and or improper equipment operation Fre...

Страница 22: ...temperature would be set too high then the GHP would not be providing the customer with the best efficiency due to extended operation run hours of the gas furnace or electric heat resulting in higher...

Страница 23: ...M 1064 1063 QUIET N A 911 048 Low 936 Max 1486 1486 EFF 1 1207 1207 EFF 2 1300 1300 COM 1107 1105 QUIET N A 947 048 High 1080 Max 1714 1714 EFF 1 1393 1393 EFF 2 1500 1500 COM 1277 1275 QUIET N A 1093...

Страница 24: ...1 1 1 0 1 0 10 2 3 2 2 2 0 2 0 1 9 1 8 1 8 1 7 1 7 15 4 8 4 7 4 2 4 1 3 9 3 8 3 7 3 6 3 5 GZ072 9 1 0 1 0 0 9 0 9 0 9 0 8 0 8 0 8 0 8 12 1 7 1 7 1 5 1 5 1 4 1 4 1 3 1 3 1 3 18 3 6 3 5 3 2 3 1 3 0 2 9...

Страница 25: ...Load 30 4 76 92 242 297 3 4 13 14 8 80 97 249 304 2 3 13 15 40 4 125 151 180 221 14 18 19 22 89 108 255 312 4 5 15 17 8 120 146 169 207 8 10 20 23 93 113 261 320 3 3 16 18 50 4 134 163 211 258 14 18...

Страница 26: ...4 5 74 90 244 299 3 4 13 15 9 0 78 95 251 306 2 3 13 16 40 4 5 122 149 183 224 14 18 19 23 87 106 257 314 4 5 15 18 9 0 117 143 172 210 8 10 20 24 91 111 263 322 3 3 16 19 50 4 5 131 160 214 261 14 1...

Страница 27: ...1 87 277 339 6 7 15 19 12 0 75 92 284 347 4 5 16 20 40 6 0 118 144 194 237 21 25 19 23 84 102 291 356 7 9 18 22 12 0 113 138 182 223 12 14 20 24 88 108 299 365 5 6 19 23 50 6 0 127 155 226 276 21 25 1...

Страница 28: ...7 0 68 84 256 313 5 7 19 23 14 0 73 89 261 319 4 5 20 25 40 7 0 117 143 182 222 15 19 21 26 81 99 277 339 7 8 22 26 14 0 114 139 170 208 11 14 22 27 86 105 283 346 5 6 23 28 50 7 0 120 147 215 263 15...

Страница 29: ...9 0 71 87 259 316 5 7 19 23 18 0 76 92 264 322 4 5 20 25 40 9 0 120 146 185 225 15 19 21 26 84 102 280 342 7 8 22 26 18 0 117 142 173 211 11 14 22 27 89 108 286 349 5 6 23 28 50 9 0 123 150 218 266 1...

Страница 30: ...eeze Sensor Fault 57 Freeze sensor is invalid or out of range Check for open sensor wire disconnected sensor not connect ed properly or abnormal sensor temp ranges Compressor Thermal Cutout in Low Sta...

Страница 31: ...pressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24volt coil The electronic control board controls the operation of the con...

Страница 32: ...ntrol of the system In this manner the service technician can run the diagnostic checkouts right at the outdoor unit using the service tool After the checkouts are completed and it is no longer necess...

Страница 33: ...00 11 52 18 970 57 135 2 774 103 217 622 34 29 227 600 12 54 18 090 58 136 2 674 104 219 604 33 27 213 600 13 55 17 260 59 138 2 579 105 221 587 32 26 200 500 14 57 16 470 60 140 2 488 106 223 571 31...

Страница 34: ...of the unit is a normal protective measure in the design of the equipment If continual lockouts occur call a mechanic immediately and have them check for the following Water flow problems Water tempe...

Отзывы: