Open Loop Well Water Systems

IMPORTANT

: Table 2 must be consulted for water quality

requirements when using open loop systems. A water sample must
be obtained and tested, with the results compared to the table.
Scaling potential should be assessed using the pH/Calcium
hardness method. If the pH is <7.5 and the calcium hardness is
<100 ppm, the potential for scaling is low. For numbers out of the
range listed, a monitoring plan must be implemented due to
probable scaling.
Other potential issues such as iron fouling, corrosion, erosion and
clogging must be considered. Careful attention to water conditions
must be exercised when considering a well water application.
Failure to perform water testing and/or applying a geothermal heat
pump to a water supply that does not fall within the accepted
quality parameters will be considered a mis--application of the unit
and resulting heat exchanger failures will not be covered under
warranty. Where a geothermal system will be used with adverse
water conditions, a suitable plate--frame heat exchanger MUST be
used to isolate the well water from the geothermal unit.
Proper testing is required to assure the well water quality is suitable
for use with water source equipment.
In conditions anticipating moderate scale formation or in brackish

water, a cupronickel heat exchanger is recommended. Copper is
adequate for ground water that is not high in mineral content.
In well water applications, water pressure must always be
maintained in the heat exchanger. This is accomplished by

installing the water solenoid valve in the leaving / outlet water line.

When using a single water well to supply both domestic water and
the heat pump, care must be taken to insure that the well can

provide sufficient flow for both.
In well water applications, a slow closing solenoid valve must be

used to prevent water hammer (hammering or stuttering sound in

the pipeline). Solenoid valve should be connected across Y1 and
COND on the interface board for all. Make sure that the VA draw

of the valve does not exceed the contact rating of the thermostat.
(See Fig. 4)
The water solenoid valve should be installed in the leaving water

line. A flow regulator valve should be located after the solenoid to
set the flow rate. The suggested flow rate is 1.5 GPM per ton if the

Entering Water Temperature (EWT) is 50

_

F or above. If below

50

_

F EWT use 2 GPM per ton. Example, a 4 ton unit with 50

_

F

EWT would require a 6 GPM flow regulator. This would be part #

FR6 (Flow Regulator) and the 6 is the GPM. If example was with
48

_

F EWT part. Refer to the

Open Loop Accessories

section in the

Geothermal System Components Catalog for more part numbers.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Discharge air configuration change is not possible on Heat

Pumps equipped with Electric Heat Option.

1

2

3

5

6

4

7

Typical Installation shown for 
Illustrion purposes only.  
Split unit not shown

9

8

10

11

12

13

14

Note

: Package unit shown. GZ unit is connected to furnace or fan coil (see page 6).

(1) Flex Duct Connection

(8) Hose Kits (optional)

(2) Low Voltage Control Connection

(9) Pressure Tank (optional)

(3) Vibration Pad

(10) P/T Ports

(4) Ball Valves

(11) Line Voltage Connection

(5) Solenoid Valve Slow Closing

(12) Electric Heater Line Voltage Disconnect

(6) Condensate Drain Connection

(13) Unit Line Voltage Disconnect

(7) Drain Valves

(14) Flow Regulator

A150775

Fig. 4 -- Example Well Water System Setup

Содержание GZ024

Страница 1: ...ualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this prod...

Страница 2: ...laims with the carrier Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt Location Clearance To maximize syst...

Страница 3: ...ons See Fig 3 Diagram shows typical vertical package unit installation and is for illustration purposes only Ensure access to Heat Pump is not restricted Note Package unit shown GZ unit is connected t...

Страница 4: ...ll to supply both domestic water and the heat pump care must be taken to insure that the well can provide sufficient flow for both In well water applications a slow closing solenoid valve must be used...

Страница 5: ...will occur Corrosion Prevention pH All 6 8 5 Monitor treat as needed 6 8 5 Minimize steel pipe below 7 and no open tanks with pH 8 Hydrogen Sulfide H2S All At H S 0 2 ppm avoid use of copper and coppe...

Страница 6: ...INSTALLATIONS Power Disconnects Air Handler Vibration Isolator Pad Fig 5 Typical Split with Air Handler Installation Vibration Isolator Pad Power Disconnects Fig 6 Typical Split with A coil Furnace In...

Страница 7: ...liquid lines affects system performance to a lesser degree provided that a solid column of liquid no flash gas is being delivered to the refrigerant metering device and that the liquid pressure at the...

Страница 8: ...tem charge Factory charge 45 ft 25 ft X 60 oz ft Total system charge 86 oz 20 ft x 60 oz ft 98 oz Additional 12 oz of R410A refrigerant required Model GZ060 with 10 ft of equivalent length of 3 8 O D...

Страница 9: ...e hoses should be used between the unit and the rigid system to avoid possible vibration Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing...

Страница 10: ...s 3 tons and smaller one valve is typical For larger two stage heat pumps there is an opportunity to save a significant amount of energy and avoid wasting water with the use of two solenoid valves one...

Страница 11: ...r piping allowing all air to bleed out until water appears at valve 6 Before restoring the power or fuel supply to the water heater adjust the temperature setting on the tank thermostat s to ensure ma...

Страница 12: ...by a pause then 7 long flashes followed by another pause and repeats this series The Wall Control will display text on the screen for the last 10 events S Exit service screens by selecting Done Non Co...

Страница 13: ...ber that all sides of the cabinet are accessible but in event the unit is placed where all sides make this difficult removal of the box may help The transformer is a 75va transformer which should prov...

Страница 14: ...IMPORTANT A160124 Communicating controls notes 1 Y2 connector ST1 is used for a utility curtailment input and is not available for use as an output for the second valve However the wiring harness exte...

Страница 15: ...esult in unit damage and or improper equipment operation If heat recovery unit is installed in an area where freezing may occur the unit must be drained during winter months to prevent heat exchanger...

Страница 16: ...ws the UI to display outdoor air temperature A150195 Fig 20 OAT Sensor Connection Compressor Start Accessories In the event of the rare occurrence of compressor starting issues such as dimming of the...

Страница 17: ...aries are dual tapped for 208 and 230 volts Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage 24 volts is ideal for best operation jThe following guidelines are rec...

Страница 18: ...access the refrigerant system at start up on package units Access should only be necessary as last resort in troubleshooting to prevent unnecessary charge issues j Check the water flow and operating...

Страница 19: ...SEC YES NO NO YES START ANTI SHORT CYCLE INITIAL POWER UP YES NO START RANDOM START UP START COUNTER NEEDED YES COUNT 2 OR COUNT 4 BLINK CODE ON STATUS LED DISPLAY OUTPUT PULSE ALR OUTPUT ON PULSE NO...

Страница 20: ...ducing the effective displacement of the compressor Full capacity is achieved by blocking these vents thus increasing the displacement to 100 A DC solenoid in the compressor controlled by a rectified...

Страница 21: ...mportant to have the Freeze1 set to the default 26_F 3 33_C CAUTION UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in unit damage and or improper equipment operation Fre...

Страница 22: ...temperature would be set too high then the GHP would not be providing the customer with the best efficiency due to extended operation run hours of the gas furnace or electric heat resulting in higher...

Страница 23: ...M 1064 1063 QUIET N A 911 048 Low 936 Max 1486 1486 EFF 1 1207 1207 EFF 2 1300 1300 COM 1107 1105 QUIET N A 947 048 High 1080 Max 1714 1714 EFF 1 1393 1393 EFF 2 1500 1500 COM 1277 1275 QUIET N A 1093...

Страница 24: ...1 1 1 0 1 0 10 2 3 2 2 2 0 2 0 1 9 1 8 1 8 1 7 1 7 15 4 8 4 7 4 2 4 1 3 9 3 8 3 7 3 6 3 5 GZ072 9 1 0 1 0 0 9 0 9 0 9 0 8 0 8 0 8 0 8 12 1 7 1 7 1 5 1 5 1 4 1 4 1 3 1 3 1 3 18 3 6 3 5 3 2 3 1 3 0 2 9...

Страница 25: ...Load 30 4 76 92 242 297 3 4 13 14 8 80 97 249 304 2 3 13 15 40 4 125 151 180 221 14 18 19 22 89 108 255 312 4 5 15 17 8 120 146 169 207 8 10 20 23 93 113 261 320 3 3 16 18 50 4 134 163 211 258 14 18...

Страница 26: ...4 5 74 90 244 299 3 4 13 15 9 0 78 95 251 306 2 3 13 16 40 4 5 122 149 183 224 14 18 19 23 87 106 257 314 4 5 15 18 9 0 117 143 172 210 8 10 20 24 91 111 263 322 3 3 16 19 50 4 5 131 160 214 261 14 1...

Страница 27: ...1 87 277 339 6 7 15 19 12 0 75 92 284 347 4 5 16 20 40 6 0 118 144 194 237 21 25 19 23 84 102 291 356 7 9 18 22 12 0 113 138 182 223 12 14 20 24 88 108 299 365 5 6 19 23 50 6 0 127 155 226 276 21 25 1...

Страница 28: ...7 0 68 84 256 313 5 7 19 23 14 0 73 89 261 319 4 5 20 25 40 7 0 117 143 182 222 15 19 21 26 81 99 277 339 7 8 22 26 14 0 114 139 170 208 11 14 22 27 86 105 283 346 5 6 23 28 50 7 0 120 147 215 263 15...

Страница 29: ...9 0 71 87 259 316 5 7 19 23 18 0 76 92 264 322 4 5 20 25 40 9 0 120 146 185 225 15 19 21 26 84 102 280 342 7 8 22 26 18 0 117 142 173 211 11 14 22 27 89 108 286 349 5 6 23 28 50 9 0 123 150 218 266 1...

Страница 30: ...eeze Sensor Fault 57 Freeze sensor is invalid or out of range Check for open sensor wire disconnected sensor not connect ed properly or abnormal sensor temp ranges Compressor Thermal Cutout in Low Sta...

Страница 31: ...pressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24volt coil The electronic control board controls the operation of the con...

Страница 32: ...ntrol of the system In this manner the service technician can run the diagnostic checkouts right at the outdoor unit using the service tool After the checkouts are completed and it is no longer necess...

Страница 33: ...00 11 52 18 970 57 135 2 774 103 217 622 34 29 227 600 12 54 18 090 58 136 2 674 104 219 604 33 27 213 600 13 55 17 260 59 138 2 579 105 221 587 32 26 200 500 14 57 16 470 60 140 2 488 106 223 571 31...

Страница 34: ...of the unit is a normal protective measure in the design of the equipment If continual lockouts occur call a mechanic immediately and have them check for the following Water flow problems Water tempe...

Отзывы: