background image

7

MATCHED SYSTEM

The GZ geothermal splits have been tested and rated with Carrier
& Bryant air handlers (fan coils) and evaporator coils (for use with

furnaces).
Use air handler or cased coil from the list below and follow the

Installation Instructions for those components.

Geothermal and Air Handler or Cased Coil Match---Up

Geothermal Split

Air Handler

Cased Coil

GZ024

F(E/V)4***003,

FB*024

C(A/N)P(V/M)P2417

GZ036

F(E/V)4***003,

F(E/V)4***005

C(A/N)P(V/M)P3617

GZ048

F(E/V)4***005

C(A/N)P(V/M)P4821

GZ060

F(E/V)4***006

C(A/N)P(V/M)P6024

GZ072

F(E/V)4***006

C(A/N)P(V/M)P6024

When using the GZ unit with a furnace, it is important to match the

CFM output of the furnace to the requirements of the GHP. For the
GZ072, the selected furnace must achieve at least 2200 CFM.

NOTE

:

The Infinity/Evolution Control may not prevent the

system from accepting a furnace with less airflow than required for

the GZ072. This is the responsibility of the installer.

REFRIGERANT LINES

!

WARNING

PERSONAL INJURY / ENVIRONMENTAL HAZARD

Failure to follow this warning could result in personal injury

or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal.
Use all service ports and open all flow–control devices,

including solenoid valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

The installation of the copper refrigerant tubing must be done with

care to obtain reliable, trouble free operation. This installation

should only be performed by qualified refrigeration service and

installation personnel.
Refrigerant lines should be routed and supported so as to prevent

the transmission of vibrations into the building structure. 75 feet as
the maximum length of interconnecting refrigerant lines in split

system heat pumps.

Beyond 75 feet, system losses become

substantial and the total refrigerant charge required can

compromise the reliability and design life of the equipment.
Refrigerant lines should be sized in accordance with those listed in
Table 3. Copper tubing must be clean and free of moisture and dirt

or debris. The suction and liquid lines should be insulated with at
least 3/8” wall, closed--cell foam rubber insulation or equivalent.

Table 3 – Valve Sizing Chart

Valve Sizing Chart

Unit Size

Line Type

Valve Conn.

Size

Allen Wrench

Size

GZ024, 036

Suction

3/4

5/16

GZ048, 060, 072

Suction

7/8

5/16

All Valves

Liquid

3/8

5/16

Some points to consider are:

S

Pressure drop (friction losses) in refrigerant suction lines reduces

system capacity and increases power consumption by as much as

2% or more, depending on the line length, number of bends, etc.

Pressure drop in liquid lines affects system performance to a lesser

degree, provided that a solid column of liquid (no flash gas) is

being delivered to the refrigerant metering device, and that the

liquid pressure at the refrigerant metering device is sufficient to

produce the required refrigerant flow.

S

Oil is continually being circulated with the refrigerant so, oil

return to the compressor is always a consideration in line sizing.

Suction lines on split system heat pumps are also hot gas lines in

the heating mode, but are treated as suction lines for sizing

purposes. If the recommended suction lines sizes are used, there

should be no problem with oil return.

S

Vertical lines should be kept to a minimum. Vertical liquid lines

will have a vertical liquid lift in either heating or cooling, and the

weight of the liquid head is added to the friction loss to arrive at

the total line pressure drop.

S

Wherever possible, the air handler should be installed at a higher

elevation than the condensing section to aid with oil return to the

compressor.

Linear vs Equivalent Line Length

Linear Line Length

-- is the actual measured length of the line

including bends. This is used to calculate the additional refrigerant

charge that must be added to the system.

Equivalent Line Length

-- is the combination of the actual length

of all the straight runs and the equivalent length of all bends valves

and fittings in a particular line. The equivalent length of a bend,

valve or fitting is equal to the length of a straight tube of the same

diameter having the same pressure drop as the particular valve or

fitting. The ASHRAE Fundamentals Handbook provides tables for

determining the equivalent length of various bends, valves and

fittings.

Connecting Refrigerant Lines

S

Use only ACR grade copper tubing and keep ends sealed until

joints are made.

S

For best performance, select routing of refrigerant lines for

minimum distance and least number of bends.

S

Size lines in accordance with Table 5.

S

Cut crimped ends off the air handler suction and liquid lines.

Connect and braze lines to the air handler.

NOTE

: The air handler is factory supplied with a holding charge

of dry nitrogen.

S

Connect and braze lines to service valves on the condensing

section.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Use a brazing shield

S

Wrap service valves with wet cloth or heat sink material.

S

Direct flame away from the valve body.

S

Valve body temperature must remain below 250

_

F to

protect the internal rubber “O” rings and seals.

S

Use nitrogen purge while brazing.

Pressurize the refrigerant lineset and air handler to 150 lbs with dry
nitrogen through the ports provided on the self service valves.

Check lineset and unit connections for leaks. Once system integrity
is verified, evacuate lineset and air handler with a good vacuum

pump to 500 microns and hold for half hour.

IMPORTANT

:

Pumpdown must never be used with heat

pumps.

Содержание GZ024

Страница 1: ...ualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this prod...

Страница 2: ...laims with the carrier Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt Location Clearance To maximize syst...

Страница 3: ...ons See Fig 3 Diagram shows typical vertical package unit installation and is for illustration purposes only Ensure access to Heat Pump is not restricted Note Package unit shown GZ unit is connected t...

Страница 4: ...ll to supply both domestic water and the heat pump care must be taken to insure that the well can provide sufficient flow for both In well water applications a slow closing solenoid valve must be used...

Страница 5: ...will occur Corrosion Prevention pH All 6 8 5 Monitor treat as needed 6 8 5 Minimize steel pipe below 7 and no open tanks with pH 8 Hydrogen Sulfide H2S All At H S 0 2 ppm avoid use of copper and coppe...

Страница 6: ...INSTALLATIONS Power Disconnects Air Handler Vibration Isolator Pad Fig 5 Typical Split with Air Handler Installation Vibration Isolator Pad Power Disconnects Fig 6 Typical Split with A coil Furnace In...

Страница 7: ...liquid lines affects system performance to a lesser degree provided that a solid column of liquid no flash gas is being delivered to the refrigerant metering device and that the liquid pressure at the...

Страница 8: ...tem charge Factory charge 45 ft 25 ft X 60 oz ft Total system charge 86 oz 20 ft x 60 oz ft 98 oz Additional 12 oz of R410A refrigerant required Model GZ060 with 10 ft of equivalent length of 3 8 O D...

Страница 9: ...e hoses should be used between the unit and the rigid system to avoid possible vibration Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing...

Страница 10: ...s 3 tons and smaller one valve is typical For larger two stage heat pumps there is an opportunity to save a significant amount of energy and avoid wasting water with the use of two solenoid valves one...

Страница 11: ...r piping allowing all air to bleed out until water appears at valve 6 Before restoring the power or fuel supply to the water heater adjust the temperature setting on the tank thermostat s to ensure ma...

Страница 12: ...by a pause then 7 long flashes followed by another pause and repeats this series The Wall Control will display text on the screen for the last 10 events S Exit service screens by selecting Done Non Co...

Страница 13: ...ber that all sides of the cabinet are accessible but in event the unit is placed where all sides make this difficult removal of the box may help The transformer is a 75va transformer which should prov...

Страница 14: ...IMPORTANT A160124 Communicating controls notes 1 Y2 connector ST1 is used for a utility curtailment input and is not available for use as an output for the second valve However the wiring harness exte...

Страница 15: ...esult in unit damage and or improper equipment operation If heat recovery unit is installed in an area where freezing may occur the unit must be drained during winter months to prevent heat exchanger...

Страница 16: ...ws the UI to display outdoor air temperature A150195 Fig 20 OAT Sensor Connection Compressor Start Accessories In the event of the rare occurrence of compressor starting issues such as dimming of the...

Страница 17: ...aries are dual tapped for 208 and 230 volts Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage 24 volts is ideal for best operation jThe following guidelines are rec...

Страница 18: ...access the refrigerant system at start up on package units Access should only be necessary as last resort in troubleshooting to prevent unnecessary charge issues j Check the water flow and operating...

Страница 19: ...SEC YES NO NO YES START ANTI SHORT CYCLE INITIAL POWER UP YES NO START RANDOM START UP START COUNTER NEEDED YES COUNT 2 OR COUNT 4 BLINK CODE ON STATUS LED DISPLAY OUTPUT PULSE ALR OUTPUT ON PULSE NO...

Страница 20: ...ducing the effective displacement of the compressor Full capacity is achieved by blocking these vents thus increasing the displacement to 100 A DC solenoid in the compressor controlled by a rectified...

Страница 21: ...mportant to have the Freeze1 set to the default 26_F 3 33_C CAUTION UNIT DAMAGE AND OR OPERATION HAZARD Failure to follow this caution may result in unit damage and or improper equipment operation Fre...

Страница 22: ...temperature would be set too high then the GHP would not be providing the customer with the best efficiency due to extended operation run hours of the gas furnace or electric heat resulting in higher...

Страница 23: ...M 1064 1063 QUIET N A 911 048 Low 936 Max 1486 1486 EFF 1 1207 1207 EFF 2 1300 1300 COM 1107 1105 QUIET N A 947 048 High 1080 Max 1714 1714 EFF 1 1393 1393 EFF 2 1500 1500 COM 1277 1275 QUIET N A 1093...

Страница 24: ...1 1 1 0 1 0 10 2 3 2 2 2 0 2 0 1 9 1 8 1 8 1 7 1 7 15 4 8 4 7 4 2 4 1 3 9 3 8 3 7 3 6 3 5 GZ072 9 1 0 1 0 0 9 0 9 0 9 0 8 0 8 0 8 0 8 12 1 7 1 7 1 5 1 5 1 4 1 4 1 3 1 3 1 3 18 3 6 3 5 3 2 3 1 3 0 2 9...

Страница 25: ...Load 30 4 76 92 242 297 3 4 13 14 8 80 97 249 304 2 3 13 15 40 4 125 151 180 221 14 18 19 22 89 108 255 312 4 5 15 17 8 120 146 169 207 8 10 20 23 93 113 261 320 3 3 16 18 50 4 134 163 211 258 14 18...

Страница 26: ...4 5 74 90 244 299 3 4 13 15 9 0 78 95 251 306 2 3 13 16 40 4 5 122 149 183 224 14 18 19 23 87 106 257 314 4 5 15 18 9 0 117 143 172 210 8 10 20 24 91 111 263 322 3 3 16 19 50 4 5 131 160 214 261 14 1...

Страница 27: ...1 87 277 339 6 7 15 19 12 0 75 92 284 347 4 5 16 20 40 6 0 118 144 194 237 21 25 19 23 84 102 291 356 7 9 18 22 12 0 113 138 182 223 12 14 20 24 88 108 299 365 5 6 19 23 50 6 0 127 155 226 276 21 25 1...

Страница 28: ...7 0 68 84 256 313 5 7 19 23 14 0 73 89 261 319 4 5 20 25 40 7 0 117 143 182 222 15 19 21 26 81 99 277 339 7 8 22 26 14 0 114 139 170 208 11 14 22 27 86 105 283 346 5 6 23 28 50 7 0 120 147 215 263 15...

Страница 29: ...9 0 71 87 259 316 5 7 19 23 18 0 76 92 264 322 4 5 20 25 40 9 0 120 146 185 225 15 19 21 26 84 102 280 342 7 8 22 26 18 0 117 142 173 211 11 14 22 27 89 108 286 349 5 6 23 28 50 9 0 123 150 218 266 1...

Страница 30: ...eeze Sensor Fault 57 Freeze sensor is invalid or out of range Check for open sensor wire disconnected sensor not connect ed properly or abnormal sensor temp ranges Compressor Thermal Cutout in Low Sta...

Страница 31: ...pressor is also protected by an internal overload attached to motor windings Compressor Control Contactor The contactor has a 24volt coil The electronic control board controls the operation of the con...

Страница 32: ...ntrol of the system In this manner the service technician can run the diagnostic checkouts right at the outdoor unit using the service tool After the checkouts are completed and it is no longer necess...

Страница 33: ...00 11 52 18 970 57 135 2 774 103 217 622 34 29 227 600 12 54 18 090 58 136 2 674 104 219 604 33 27 213 600 13 55 17 260 59 138 2 579 105 221 587 32 26 200 500 14 57 16 470 60 140 2 488 106 223 571 31...

Страница 34: ...of the unit is a normal protective measure in the design of the equipment If continual lockouts occur call a mechanic immediately and have them check for the following Water flow problems Water tempe...

Отзывы: