Nov-21
Page 95 of 132
59812-K001 Rev 10
A list of the fault that are not listed in the Event Log are detailed below.
Fault
Description
Section
Continuous
Backup
Alarm
A backup alarm is indicated without a deviation or
average alarm.
Control Panel Reset
The Control Panel is continuously resetting every 2
seconds.
Replace EEPROM
The EEPROM has reached the guaranteed number of
write operations.
5.2
FAULT DIAGNOSTICS AND REMEDIES
5.2.1
Backup Alarm Test Failure
A Backup Alarm Test is performed manually via the Test Menu, see section 3.5, or automatically during
the daily system check at 16:00hrs. If a failure occurs during the test a Backup Alarm Test fault is
indicated, see section 5.1.2
Figure 134
Backup Alarm Fault
An inspection of the engine event log, see section 3.6, will list the event:
Back-Up Test Failed
Eng X det Y
5.2.1.1
Single Detector in fault
Having established which detector is in fault it is necessary to establish the cause of the fault using the
following steps.
1.
Swap the detector with a known working detector.
2.
Reset the Control Panel.
3.
Perform a Backup Alarm Test via the Test Menu, see Error! Reference source not found.
If the fault indication remains at the original position return the swapped detectors to the initial
positions go to item 4
If the fault indication moves to the new position of the detector, the detector has failed and
should be replaced.
4.
Open the Junction Box lid. For the indicated failed detector position check the connection of the
backup alarm wire (grey wire).
5.
Using a wire link connect the backup alarm terminal (grey wire) to the 0v terminal (blue wire) for
the indicated failed detector position.
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...