
Nov-21
Page 42 of 132
59812-K001 Rev 10
2.6.4
Junction Box to Detector Connections
At the Junction Box strip the Detector cables to the required length. The cables should be long enough
to reach easily from the gland to the terminals. Remove approximately 1cm of the outer sheath to expose
the cable screen as shown below
Figure 30
Detector cable, stripped.
Feed the cable through a metal EMC gland, e.g. Lapp Kabel Skintop MS-SC-M-XL range, ensuring that
the metal prongs make contact with the exposed cable screen as shown below
Figure 31
Detector cable, EMC Gland assembly
Connect the cable via the relevant Detector position hole in the Junction Box.
Figure 32
Detector cable, EMC Gland & Junction Box
Connect the wires into the Junction Box terminals as detailed in the table below and tighten the gland.
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...