Nov-21
Page 107 of 132
59812-K001 Rev 10
If the voltage is within the limits replace the Main Control Processor Board.
9.
Remove the power from the system
10.
Disconnect the power cable between the Interface board and Main Control Processor Board.
11.
Check that the connector pins are clean and there is no oxidation. If necessary, lightly clean the
pins with emery paper.
12.
Reconnect the cable and switch on the system.
13.
If the Control Panel continues to reset replace the Main Control Processor Board.
5.2.12
Replace EEPROM
The EEPROM is the flash memory which stores the system configuration data and the Event Log data in
the Graviner Mk6 OMD system.
The EEPROM is device IC17 on the Main Control Processor Board (part number 1-44782-K071-02).
(IC 17)
has reached the maximum number of write cycles recommended by the chip manufacturer and should
now be replaced. The EEPROM device manufacturer guarantees a minimum of 10,000 write cycles.
NOTE:-
This message is advisory only, all other features and functions of the OMD Mk6 will continue to
operate normally and the ability to detect oil mist is not affected.
A read/write failure could mean that recent Event Log data is not stored and any changes made to the
configurable engine parameters may not be saved.
Due to the memory capacity with normal operation of the system it is expected that memory will last
over 10 years before the memory limit is met. Earlier failure of the EEPROM may be due to underlying
faults being recorded in the event log. The event log should be examined prior to replacing the EEPROM.
Figure 150
Replace EEPROM
The action required to remove this warning message depends on the version of the Main Control
Processor Board fitted in the Control Panel.
On earlier versions of the PCB, the EEPROM (device IC17 in the images shown below) is soldered directly
to the Processor board. The EEPROM device cannot be de-soldered without the risk of damaging the PCB
and so requires the Main Control Processor Board to be replaced.
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...