Nov-21
Page 43 of 132
59812-K001 Rev 10
Connector Pin
No.
Colour of wire
Function
Last Detector
Function
1
Pink
Comms Out -
TB10 EOL-
1
White
Comms In -
C- in
2
Yellow
Comms In+
C+ in
2
Brown
Comms Out +
TB10 EOL+
3
Grey
Backup Alarm
Alarm Back-up
5
Blue
0v supply
0V
6
Red
24v supply
+24V
Centre
Screen
Cable screen
Cable screen
Figure 33
Close-up of Detector cable, EMC Gland assembly
When complete the Junction Box wiring should look like the photograph below.