Nov-21
Page 24 of 132
59812-K001 Rev 10
2.2
CONTROL PANEL CABLING
24v DC Input supply
The Mk6 Control Panel should be powered from a floating 24v DC supply (+30% -25%) suitably rated
depending on the number of detectors connected.
PLEASE NOTE: - The Control Panel may not operate correctly if the external 24v power supply
is referenced to the vessel earth and there is also a risk the input protection circuitry in the units
could be damaged.
Cables should be segregated from high voltage cables and follow good instal lation practice.
Cable type-2 Cores + Earth, CSA 2.5mm
2
(50/0.25mm), flexible stranded bare copper conductors, low
smoke halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath grey,
outside diameter 9.8mm, operating temperature 0ºC + 80ºC.
Suggested cables
Lapp Kabel
CY cable 3 core 2.5mm
2
Prysmian
LSM-HF 3 core 2.5mm
2
Helkama
LKAM-HF 3 core 2.5mm
2
Refer Error! Reference source not found. for connector location.
Refer Figure 36 for wiring drawing.
Communications
Cable type Individually screened 2 pair data cable, 24AWG, low capacitance, low smoke halogen free.
Outer diameter 7mm (max)
Cables should be segregated from high voltage cables and follow good installation practice
Approved cables:
FS Cables
2402PIFFH
Beldon
9729
Helkama
RFE-HF(i) 2x2x0.75
Jinro
60V RCOP(IS)
The above cable should be used to connect between the Control Panel and the Junction Boxes.
Refer Error! Reference source not found. for connector location.
Refer Figure 36 for wiring drawing.
Relay Outputs
The relay outputs are rated at 30v DC at 1amps.
2 Cores + Earth, CSA 2.5mm
2
(50/0.25mm), flexible stranded bare copper conductors, low smoke
halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath grey, outside
diameter 9.8mm, operating temperature 0
o
C + 80
o
C.
Cables should be segregated from high voltage cables and follow good installation practice
Approved cables:
Lapp Kabel
CY cable 3 core 2.5mm2
Prysmian
LSM-HF 3 core 2.5mm2
Helkama
LKAM-HF 3 core 2.5mm2
Refer Error! Reference source not found. for connector location.
Refer Figure 36 for wiring drawing.
2.3
JUNCTION BOX MOUNTING
The Junction Box is available with 20mm input glands, (1-D4720-001-14) or 25mm input glands, (1-
53836-K224-14), and is designed for on-engine mounting. It is recommended that the box is installed as
near to the centre of the engine as possible to minimise Detector cable lengths. Mounting is via the four
M6 locating holes in the box. Sufficient space must be left around the Junction Box to allow access to
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...