Nov-21
Page 36 of 132
59812-K001 Rev 10
Figure 20
Power connections
The Control Panel should be connected from the earth stud to a suitable earthing point.
Where permitted by the vessel approval authority only one power cable may be required. Connections
can be made to either power input 1 or power input 2.
Both the earth and the screen of the cable should be connected to earth at the 24v DC power supply.
2.6.2
Relay Cables
The connection to the Slowdown/Shutdown relays, Common Alarm relay, and Fault relay at the Control
Panel should be made using screened cable. For each of the relay connections strip the cable to the
required length to connect to the terminals in the Control Panel. Then remove approximately 1cm of the
outer sheath to expose the cable screen as shown below.
Cables should be segregated from high voltage cables and follow good installation practice
Figure 21
Control Panel relay cable assembly
Содержание Graviner Mk6
Страница 16: ...Nov 21 Page 16 of 132 59812 K001 Rev 10 Height 309mm Width 559mm Depth 118 5mm Weight 8 7kg ...
Страница 26: ...Nov 21 Page 26 of 132 59812 K001 Rev 10 Figure 9 Junction Box Installation ...
Страница 29: ...Nov 21 Page 29 of 132 59812 K001 Rev 10 Figure 12 Detector Head Installation ...
Страница 30: ...Nov 21 Page 30 of 132 59812 K001 Rev 10 Figure 13 Detector Head Installation Short Sample Pipe ...
Страница 46: ...Nov 21 Page 46 of 132 59812 K001 Rev 10 Figure 36 System Drawing ...
Страница 47: ...Nov 21 Page 47 of 132 59812 K001 Rev 10 Figure 37 Wiring Diagram ...
Страница 112: ...Nov 21 Page 112 of 132 59812 K001 Rev 10 6 6 1 CONTROL PANEL Figure 158 Control Panel Door ...
Страница 123: ...Nov 21 Page 123 of 132 59812 K001 Rev 10 ...
Страница 126: ...Nov 21 Page 126 of 132 59812 K001 Rev 10 ...
Страница 129: ...Nov 21 Page 129 of 132 59812 K001 Rev 10 ...