2. Nomenclature and General Technical Features
Table 1 - Operating Limits
Unit
30EV_15
30EX_15
Minimum fl ow on evaporator
m
3
/h
4,2
4,4
Maximum fl ow on evaporator
m
3
/h
15,3
18,2
Maximum
outdoor temperature
°C
45
45
Minimum outdoor temperature
°C
10
10
Maximum REWT (evaporator)¹
°C
35
35
Minimum REWT (evaporator)¹
°C
6
6
Maximum ULWT (evaporator)²
°C
35
35
Minimum ULWT (evaporator)²
°C
5
5
Minimum temperature delta
3
°C
3
3
Maximum temperature delta
3
°C
10
10
3 0 E X A 1 5 2 2 6 M A H - - - S
30E Air Conditioning Modular
S
Standard
X
Fixed Speed
-
Reserved digits
V
Variable Speed
-
No control (slave only)
H Standard HIC (w/o Modbus)
B
Standard HIC (w/ Modbus)
15 15TR
- -
A Y Victaulic - Type Connection
B
Power Factor Correction Capacitor
(30EXA only)
22 220V
38 380V
44 440V
6
60Hz
M Master
E
Slave
Frequency
A
Reserved Digits
Machine
Request Type
Module Type
Unit Type *
Design Series
Accessories
Controls
Nominal Capacity
Voltage
C
Y Victaulic - Type conn
Power Factor Correction Capacitor
(30EXA only)
BC1
– Communication terminals
BC2
– Field terminals
CMCT
– Condensor Middle Temperature Sensor
DIST
– Discharge Temperature Sensor
DPS
– Diff erential Pressure Switch
FSC
– Fixed Compressor
OAT
– Environment Temperature Sensor
RLWT
– System Water Outlet Temperature Sensor
REWT
– System Water Inlet Temperature Sensor
SST
– Saturated Suction Temperature Sensor
SUCT
– Suction Temperature Sensor
VSC
– Inverter Compressor
ULWT
– Unit Water Outlet Temperature Sensor
FLWD
– Diff erence of temperature between system inlet and outlet at full load
WP
– Water Pump
WV
– Water Valve
WVSCSDT
– Water valve opening delay
WFC
– Flow switch sensor
FP
– Power factor
CFP
– Power Factor Correction Capacitor
Legend
:
* Inverter unit will always be the master machine.
Notes:
- For continuous operation, the maximum temperature delta (REWT-ULWT) should not exceed 10 ° C.
1
For continuous operation, REWT must be within the range of 8.0 ° C to 20.0 ° C.
2
The standard control setpoint is 5 ° to 14 ° C. This value may vary depending on the FLWD of the project and the unit
number confi gured in the control. In continuous operation at full load the maximum ULWT shall not exceed 15.0 ° C. For
more details refer to the Attachment III in this manual.
3
Refer to the Technical Catalogue - Performance Data section for case-by-case limits.