Table 3a - Inverter
Systems
In an Inverter system, the Inverter module will always be the master machine.
Table 3b -
Fixed Systems
In the event of a defect in the master unit, the system will continue to operate, however, it is possible to make one of the fi xed units (fi xed and
slave) 3 or more) in master machine, changing the addressing. In this case, disconnect the communication cable from the master unit and
switch the water sensors to the new master units. Information valid for both Inverter and Fixed systems.
NOTE
To ensure the other units in the system continue operating in the event of power loss from the Master and slave units 1, make sure to connect
the 4 (four) communication cables of terminal BC1 (A, B, 12VDC and GND) + one source 12VDC/1A (connect to the terminals 12VDC e GND).
NOTE
2. Nomenclature and General Technical Features (cont.)
MODELS
Nominal
Capacity (TR)
Sequence of Installation
(Inverter Machine, address 0000, will always be the Master)
In
ve
rt
er
Lin
e
30EVA15
15
(01x) 3 (01x) 30EXA15
30
(01x) 3 (02x) 30EXA15
45
(01x) 3 (03x) 30EXA15
60
(01x) 3 (04x) 30EXA15
75
(01x) 3 (05x) 30EXA15
90
(01x) 3 (06x) 30EXA15
105
(01x) 3 (07x) 30EXA15
120
MODELS
Nominal
Capacity (TR)
Sequence of Installation
(Machine, address 0000 will always be the Master)
Fix
e
d Line
01x 30EXA15
15
02x 30EXA15
30
03x 30EXA15
45
04x 30EXA15
60
05x 30EXA15
75
06x 30EXA15
90
07x 30EXA15
105
08x 30EXA15
120