Reading and Writing map
When using an RS485 converter> 232, do not power it from the Gateway.
NOTE
5. Operation (cont.)
5. Electrical Connection:
RS485 - Closed
Protocol. It comes
from Cond. or HMI
RS485 - Modbus RTU
Protocol. Go to
Supervisory
220VAC
GATEWAY
A1 A2
B1 B2
L N
Input Register (Function 04) - CHILLER 1
Address
Description
Comment
H0001
Type of System
See the "Type of System" table (Analyze on Hex)
H0002
Error Code
H0003
Outlet Water Temperature (INT)
H0004
Inlet Water Temperature (INT)
Chiller <2, referring to Chiller unit. Chiller> 2, referring to the system.
H0005
Outdoor Temperature
H0006
Middle Condenser Temperature
H0007
Suction Temperature
H0008
Discharge Temperature Comp.1
H0009
Discharge Temperature Comp.2
H000A
Saturated Suction Temperature
H000B
Reserve
H000C
Heatsink Temperature (Inverter only)
H000D
DIP setting
See in the detailed DIP setting section
H000E
Comp Current 1 (Fixed)
Multiply the reading by 0.25
H000F
Comp Current 2
Multiply the reading by 0.25
H0010
Digital inputs (DI)
Bit5-0 means entries 6-1 (See Table "DI")
H0011
Digital Outputs (DO)
Bit4-0 means outputs 5-1 (See table "DO")
H0012
Comp Frequency (Inv)
H0013
Comp Current (Inv)
Multiply the reading by 0.25
H0014
DC BUS Voltage (Inverter only)
H0015
Cond Motor Speed
RPM
H0016
System demand
%
H0017
Reserve
H0018
Mainboard Software Version
H0019
Reserve
H001A
Outlet Water Temperature (FRACTION)