![Carrier AQUASMART 30EV Series Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/carrier/aquasmart-30ev-series/aquasmart-30ev-series_installation-operation-and-maintenance_2562371047.webp)
47
Type of System
Table DI
Table DO
Address: H0001
System Type:
High
Low
01
18
Fixed 15
01
19
Fixed 30
01
1A
Fixed 45
01
1B
Fixed 60
01
1C
Fixed 75
01
1D
Fixed 90
01
1E
Fixed 105
01
1F
Fixed 120
Address: H0001
System Type:
High
Low
00
08
Inverter 15
00
09
Inverter 30
00
0A
Inverter 45
00
0B
Inverter 60
00
0C
Inverter 75
00
0D
Inverter 90
00
0E
Inverter 105
00
0F
Inverter 120
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
Description
High Pressure
Switch
Low Pressure
Switch
Emergency
WFC
Remote ON/OFF
DPS
Description
High Pressure
Switch
Low Pressure
Switch
Emergency
Flow Sensor
Remote On-Off
Water diff erential
pressure switch
0 - Closed
1 - Opened
0 - Ok
1 - Alarmed
0 - Ok
1 - Alarmed
0 - Ok
1 - Alarmed
0 - Ok
1 - No fl ow
0 - Turn on
1 - Turn off
0 - Ok
1 - Alarmed
0 - Closed
1 - Opened
0 - No error
1 - Alarmed
0 - No error
1 - Alarmed
0 - No error
1 - Alarmed
0 - With Flow
1 - No Flow
0 - On
1 - Off
0 - No error
1 - Alarmed
Comments
Only for
Chiller 1
Only for Chiller 1
bit 4
bit 3
bit 2
bit 1
bit 0
Description
Water Pump
(WP)
Crankcase
Heater (CH)
Water Valve
(WV)
Fixed Speed
Compressor 2
Remote error
Fixed Speed
Compressor 1
Description
Water Pump
(WP)
Crankcase
Heater (CH)
Water Valve
(WV)
Fixed Speed
Compressor 2
Remote alarm
Fixed Compressor 1
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - No alarm
1 - Alarmed
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - OFF
1 - ON
0 - No error
1 - With error
0 - OFF
1 - ON
Comments
Only for
Chiller 1
INVERTER
FIXED