5. Operation (cont.)
Reading and Writing map (Cont.)
Input Register (Function 04) - CHILLER 3-16
Address
Description
Comment
H0201-701
Reserve
H0202-702
Error Code
H0203-703
Outlet Water Temperature (INT)
H0204-704
Reserve
H0205-705
Outdoor Temperature
H0206-706
Middle Condenser Temperature
H0207-707
Suction Temperature
H0208-708
Discharge Temperature Comp.1
H0209-709
Discharge Temperature Comp.2
H020A-70A
Saturated Suction Temperature
H020B-70B
Reserve
H020C-70C
Reserve
H020D-70D
DIP adjustment
See the detailed DIP setting section
H020E-70E
Comp Current 1
Multiply the reading by 0.25
H020F-70F
Comp Current 2
Multiply the reading by 0.25
H0210-710
Digital inputs (DI)
Bit5-0 means entries 6-1 (See Table "DI")
H0211-711
Digital Outputs (DO)
Bit4-0 means outputs 5-1 (See table "DO")
H0212-712
Reserve
H0213-713
Reserve
H0214-714
Reserve
H0215-715
Cond Motor Speed
RPM
H0216-716
Reserve
H0217-717
Reserve
H0218-718
Main Software Version
H0219-719
Reserve
H021A-71A
Outlet Water Temperature (FRACTION)
H021B-71B
Reserve
Holding Register (Function 03/16) - HMI
Address
Description
Comment
H0001
On / Off
1 - On / 0 - Off
H0002
Set Point
Allowed values: according to the water delta
H0003
Reserve
EOL test. Only applied to the factory. (Do not use)
H0004
Reserve
H0005
Gateway Version