background image

38

Recommendations for maintenance and cleaning of 
mChe (microchannel) condenser coils

• 

Regular cleaning of the coil surface is essential for 
correct unit operation. 

• 

Eliminating contamination and removal of harmful residue 
will increase the operating life of the coils and the unit.

• 

The maintenance and cleaning procedures below are 
part of the regular maintenance and will prolong the 
life of the coils.

• 

Specific recommendation in case of snow: For long 

term storage, regularly check that no snow has 
accumulated on the unit coils.

Products qualified as suitable for cleaning untreated 
MCHE coils are available from the Carrier spare parts 
network. After cleaning, rinsing of the coil is mandatory 
(see Carrier standard RW01--25). The use of any other 
cleaning product is strictly prohibited.

• 

Remove all foreign objects or fragments/debris 
attached to the coil surface or wedged between the 
chassis and the supports.

• 

Use a low-pressure dry air jet to remove all traces of 

dust from the coil.

• 

Wear the personal protection equipment, including 
safety glasses and or mask, waterproof clothes and 
safety gloves. It is recommended to wear clothing that 
covers the whole body.

WARNING: Never use pressurised water without a large 
diffuser. Concentrated and/or rotating water jets are 
strictly forbidden.

Never use a fluid with a temperature above 45°C to clean 
the air heat exchangers.

Correct and frequent cleaning (approximately every three 
months) will prevent 2/3 of the corrosion problems. 
Protect the control box, the motorized ball valve and the 
VFD during cleaning operations. Don't forget to remove 
protections after cleaning operations.

11.7 - Evaporator maintenance

Check that:

• 

The insulating foam is intact and securely in place.

• 

The cooler heaters are operating, secure and correctly 
positioned.

• 

The water-side connections are clean and show no 
sign of leakage.

11.8 - compressor maintenance

11.8.1 - oil separator

Check the correct operation of the heaters and check that 
they are properly attached to the oil separator shell.

11.8.2 - Integral oil filter change

As system cleanliness is critical to reliable system operation, 

there is a filter in the oil line at the oil separator outlet. 

The oil filter is specified to provide a high level of filtration 

(5 μm) required for long bearing life.

The filter should be checked after the first 500 hours of 
operation, and every subsequent 2000 hours. The filter should 

be replaced at any time when the pressure differential 

across the filter exceeds 200 kPa (2 bar). 

The pressure drop across the filter can be determined by 
measuring the pressure at the filter service port and the oil 

pressure port. The difference in these two pressures will be 

the pressure drop across the filter, check valve, and solenoid 

valve. The pressure drop across the check valve and solenoid 
valve is approximately 40 kPa (0.4 bar), which should be 
subtracted from the two oil pressure measurements to give 

the oil filter pressure drop.

11.8.3 - Compressor rotation control

Correct compressor rotation is one of the most critical 
application considerations. Reverse rotation, even for a 
very short duration, damages the compressor.

The reverse rotation protection scheme must be able to 
determine the direction of rotation and stop the compressor 
within 300 ms. Reverse rotation is most likely to occur 
when-ever the wiring to the compressor terminals is 
disturbed.

To minimise the opportunity for reverse rotation, the follow-
ing procedure must be applied. Rewire the power cables to 
the compressor terminal pin as originally wired.

For replacement of the compressor, a low pressure switch 
is included with the compressor. This low pressure switch 
should be temporarily installed as a hard safety on the high 
pressure part of the compressor. The purpose of this switch 
is to protect the compressor against any wiring errors at 
the compressor terminal pin. The electrical contact of the 
switch would be wired in series with the high pressure switch. 
The switch will remain in place until the compressor has 

been started and direction of rotation has been verified; at 

this point, the switch will be removed. 

The switch that has been selected for detecting reverse 
rotation is Carrier part number HK01CB001. This switch 
opens the contacts when the pressure falls below 7 kPa. The 
switch is a manual reset type that can be reset after the 
pressure has once again risen above 70 kPa. It is critical 
that the switch be a  manual reset type to preclude the 
compressor from short cycling in the reverse direction.

11.9 -  Variable frequency drive maintenance

CAUTION: Before any work on the VFD ensure that the 
circuit is isolated and there is no voltage present. Note 
that it may take 5 minutes for the circuit capacitors to 
fully discharge after isolating the circuit. Only 
appropriately qualified personnel are authorised to work 
on the VFD.

In case of any alarm or persistent problem related to the 
VFD, contact Carrier Service.

The VFDs fitted with 30XAV-ZE units do not require an 

insulation test, even if being replaced; they are 

systematically verified before delivery. Moreover, the 
filtering components installed in the VFD can falsify the 

measurement and may even be damaged. If there is a need 
to test the insulation of the unit components (fan motors 
and pumps, cables, etc.), the VFD must be disconnected at 
the power circuit.

Содержание AquaForce PUREtec 30XAV-ZE 401

Страница 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Страница 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Страница 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Страница 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Страница 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Страница 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Страница 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Страница 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Страница 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Страница 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Страница 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Страница 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Страница 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Страница 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Страница 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Страница 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Страница 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Страница 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Страница 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Страница 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Страница 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Страница 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Страница 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Страница 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Страница 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Страница 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Страница 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Страница 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Страница 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Страница 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Страница 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Страница 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Страница 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Страница 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Страница 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Страница 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Страница 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Страница 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Страница 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Страница 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Страница 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Отзывы: