17
4.2 - Electrical data 30XaV-ZE
30XaV-ZE
401
501
551
651
701
851
901
Power circuit
Voltage range
V-ph-Hz
400-3-50±10%
control circuit supply
24 V via internal transformer
start-up current*
Not Applicable (less than the operating current)
Power factor**
-
Maximum***
0.90-0.92
Cosine phi
> 0.98
Total harmonic distortion
***
%
35-45
Maximum unit power input****
Circuit 1
†
kW
167
191
220
140
173
173
191
Circuit 2
†
kW
-
-
-
140
140
173
191
Option 81
kW
-
-
-
280
313
346
383
nominal unit current draw
††
Circuit 1
†
A
203
239
270
170
206
206
229
Circuit 2
†
A
-
-
-
170
170
206
229
Option 81
A
-
-
-
340
376
412
457
Maximum unit current draw (Un)****
Circuit 1
A
268
304
348
220
275
275
306
Circuit 2
A
-
-
-
220
220
275
306
Option 81
A
-
-
-
441
496
550
611
Maximum unit current draw (Un-10%)***
Circuit 1
†
A
283
322
368
231
294
294
327
Circuit 2
†
A
-
-
-
231
231
294
327
Option 81
A
-
-
-
462
525
588
654
*
Instantaneous start-up current
** May vary depending on the intensity ratio of short circuit / maximum intensity transformer installation
*** Values obtained at operation with maximum unit power input.
**** Values obtained at operation with maximum unit power input. Values given on the unit nameplate.
†
When the machines are equipped with two power supplies, circuit 1 is intended to supply the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B
†† Values obtained at standard Eurovent operating condition: Air 35 °C, water 12/7 °C.
4.3 - short-circuit stability current for 30XaV-ZE units
short-circuit stability current (Tn system)*
30XaV-ZE
401
501
551
651
701
851
901
standard unit
short-time (1s) assigned current lcw / Peak current lpk
Circuit 1
kA
-
8/37
10/40
7.5/30
13/37
13/37
14/40
Circuit 2
kA
-
-
-
7.5/30
7,5/30
13/37
14/40
assigned conditional short-circuit current Icc/Icf
Circuit 1
kA
50
-
-
-
-
-
-
With fuses upstream - maximum fuse values assigned (gl/gG)
Circuit 1
A
-
630
630
400
500
500
630
Circuit 2
A
-
-
-
400
400
500
630
With fuses upstream - assigned conditional short circuit current Icc/Icf
Circuit 1
kA
-
50
50
50
50
50
50
Circuit 2
kA
-
-
-
50
50
50
50
Units with option 81 or 70d
assigned conditionnal short circuit current Icc/Icf
Circuit 1
kA*
-
50
50
50
50
50
50
Circuit 2
kA*
-
-
-
50
50
50
50
Option 81
kA*
-
-
-
50
50
50
50
*
TN system (earthing system type)