background image

36

11.2 - level 2 maintenance

This level requires specific expertise in electrical, hydraulic 

and mechanical systems.
The frequency of this maintenance level may be monthly 

or annual, depending on the verification type.

In these cases, the following maintenance operations are 

recommended.

Carry out all level 1 operations, then: 

• 

At least once a year, tighten the power circuit 

electrical connections (refer to the table  

10.4 - Tightening torques).

• 

Check and tighten all control/command connections, 
if required (refer to the tightening torques table).

• 

Check the differential switches for correct operation 
every 6 months.

• 

Remove the dust and clean the interior of the control 

boxes, if required. Check filter cleanliness (if present).

• 

Check the presence and the condition of the electrical 
protection devices.

• 

Replace the fuses every 3 years or every 15000 hours 
(age-hardening).

• 

Replace the control box cooling fans every 5 years.

• 

Check the height of the anti-vibration mountings 
(located between the compressor rails and the unit 
chassis) after 5 years of operation, and then each year.
When the total minimum height of the mountings is 
less than 25 mm replace the mountings

• 

Verify the hydronic connections.

• 

Purge the water circuit.

• 

Clean the water filter (see chapter 7- "Water 

Connections").

• 

Check the unit operating parameters and compare 
them with the previous inspection.

• 

Keep and maintain a maintenance sheet, attached to 
each HVAC unit.

• 

Check, inside the control box, the presence of voltage 
on the terminal connection of the cooler heaters and 
drives (activate the quick test mode to energise the 
heaters).

WARNING: For all these operations take adequate safety 
measures: use appropriate PPE (personal protective 
equipment), comply with all industry and local 
regulations, use common sense.

11.3 - level 3 (or higher) maintenance

The maintenance at this level requires specific skills/

approval/tools and expertise. Only the manufacturer, his 
representative or authorised agent are permitted to carry 
out this work. These maintenance operations concern for 
example:

• 

A major component replacement (compressor, evapo-
rator)

• 

Any intervention on the refrigerant circuit (handling 
refrigerant)

• 

Changing of parameters set at the factory (application 
change)

• 

Removal or dismantling of the HVAC unit

• 

Any intervention due to a missed established mainte-
nance operation

• 

Any intervention covered by the warranty. 

 

11 - sTandard MaInTEnancE

To ensure optimal efficiency and reliability of the units, we 

recommend establishing a maintenance contract with your 
local Carrier Service organisation. This contract will 
include regular inspections by Carrier Service specialists 
so that no serious damage can occur.

A Carrier Service maintenance contract is the best way to 
ensure the maximum operating life for your equipment 
and, through the expertise of Carrier technicians, provides 
the ideal way to manage your system cost effectively.

Air conditioning equipment must be maintained by profes-
sional technicians, whilst routine checks can be carried out 
locally by specialised technicians (refer to the standard 
EN 378-4).

All refrigerant charging, removal and draining operations 

must be carried out by a qualified technician and with the 

correct equipment for the unit. Any inappropriate 

handling can lead to uncontrolled fluid or pressure leaks.

WARNING: Before doing any work on the machine 
ensure that the power is switched off. If a refrigerant 
circuit is opened, it must be evacuated, recharged and 
tested for leaks. Before any operation on a refrigerant 
circuit, it is necessary to remove the complete refrigerant 
charge from the unit with a refrigerant charge recovery 
unit.

simple preventive maintenance will allow you to get the 
best performance from your hVaC unit:

• 

Improved cooling performance.

• 

Reduced power consumption.

• 

Prevention of accidental component failure.

• 

Prevention of major time-consuming and costly inter-
ventions.

• 

Protection of the environment.

There are five maintenance levels for HVAC units, as 
defined by the AFNOR X60-010 standard.

NOTE: Any deviation or non-observation of these 
maintenance criteria will render the guarantee conditions 
for the HVAC unit null and void, and the manufacturer, 
Carrier France, will no longer be responsible.

11.1 - level 1 maintenance

These simple procedures can be carried out by the user:

• 

Check for traces of oil (indicates a refrigerant leak).

• 

Check for missing / damaged protective devices, and 
improperly closed doors / covers.

• 

Check and record alarms (see 30XAV-ZE control 
manual)

• 

Check the clogging state of filters of aeration openings 

of the control box.

General visual inspection for any signs of deterioration.

Содержание AquaForce PUREtec 30XAV-ZE 401

Страница 1: ...ariable Speed Air Cooled Screw Chillers AquaForce PUREtec with R1234ze E 30XAV ZE 401 901 nominal cooling capacity 400 900 kW 50 hz Original document InsTallaTIon oPEraTIon and MaInTEnancE InsTrUcTIon...

Страница 2: ...CAL CONNECTION 19 5 1 Power supply 19 5 2 Voltage phase imbalance 19 5 3 Power connection disconnect switch 19 5 4 Recommended wire sections 19 5 5 Power cable entry 19 5 6 Field control wiring 20 5 7...

Страница 3: ...31 9 10 Fans 31 9 11 Electronic expansion valve EXV 32 9 12 Moisture indicator 32 9 13 Filter drier 32 9 14 Sensors 32 9 15 Service valve option 92 33 9 16 Variable frequency drive 33 10 options 34 1...

Страница 4: ...oom installation Local building codes and safety standards shall be followed In absence of local codes and standards please refer to EN 378 2012 Safety requirements for substances classified A2 or to...

Страница 5: ...the refrigerant using a proper refrigerant reclaim device and reclaim cylinders The units can also be lifted with slings using only the designated lifting points marked on the unit Use slings with the...

Страница 6: ...lue Reactivate HP soft See dedicated Quick test function CAUTION If the test leads to replacing the pressure switch it is necessary to recover the refrigerant charge these pressure switches are not in...

Страница 7: ...n equipment failure carry out a refrigerant analysis at a specialist laboratory If required change the refrigerant following a procedure such as that described in NF E29 795 If the refrigerant circuit...

Страница 8: ...d with dry nitrogen Refrigerant in contact with an open flame produces toxic gases The necessary protection equipment must be available and appropriate fire extinguishers for the system and the refrig...

Страница 9: ...use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is...

Страница 10: ...ems and they do not require earthquake resistance Earthquake resistance has not been verified CAUTION Only use slings at the designated lifting points which are marked on the unit Before siting the un...

Страница 11: ...the protection of moving parts Verify the accessibility for maintenance or repair and to check the piping Verify the status of the valves Verify the quality of the thermal insulation and of the vapou...

Страница 12: ...he space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporator tube removal Water inlet for standard unit For options 100A 100C 1...

Страница 13: ...e close to walls please refer to chapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see no...

Страница 14: ...hapters 3 8 3 9 Distance to the wall of this document to determine the space required Legend All dimensions are given in mm Required clearances for maintenance see note Recommended space for evaporato...

Страница 15: ...sory supplied loose at the time of purchase can be added NOTES Drawings are not contractually binding Before designing an installation consult the certified dimensional drawings available on request F...

Страница 16: ...rol Minimum capacity 10 10 10 10 10 10 10 Condensers All aluminium Micro Channel Heat Exchanger MCHE Fans Standard unit Axial FLYING BIRD IV fans with rotating shroud Quantity 9 10 12 14 16 18 20 Maxi...

Страница 17: ...eration with maximum unit power input Values obtained at operation with maximum unit power input Values given on the unit nameplate When the machines are equipped with two power supplies circuit 1 is...

Страница 18: ...transformer 4 Overcurrent protection of the power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s is are of a type suitable for power in...

Страница 19: ...s to the general disconnect isolator switch are designed for the number and type of wires listed in column 2 of the table on the next page The calculations are based on the maximum machine current see...

Страница 20: ...01 2x240 1x185 260 XLPE 2x185 450 PVC 501 2x240 1x240 280 XLPE 2x240 480 PVC 551 2x240 1x240 250 XLPE 2x185 350 XLPE 651 2x240 2x240 1x150 1x150 260 XLPE 2x185 2x185 550 PVC 701 2x240 2x240 1 x 240 1...

Страница 21: ...be protected against freeze by using a freeze protection solution by the installer For start ups with air temperature below 5 C the machine must be equipped with option 41A Evaporator water temperatu...

Страница 22: ...upied mode 6 5 System minimum water volume Whichever the system the water loop minimum capacity is given by the formula Capacity Cap kW x N litres Application N Normal air conditioning 3 25 Process ty...

Страница 23: ...ne month the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration CAUTION Filling completing and draining the water circuit charge must be done...

Страница 24: ...93 3 Relief valve 4 Available pressure water pump 5 Water drain valve 6 Flow switch for the evaporator 7 Evaporator 8 Evaporator heater for freeze protection option 41A 41B 9 Heater for freeze protect...

Страница 25: ...ow mandatory Elbow mandatory Elbow mandatory For installation that requires thicker insulation it is advised to use a pipe reduction or an elbow to avoid the closest component When straight pipe is no...

Страница 26: ...tected by an antifreeze solution and will not be used during freezing weather conditions draining of the cooler and outdoor piping is mandatory Damage due to freezing is not covered by the warranty 7...

Страница 27: ...h unit controls its own water pump If there is only one common pump and in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing co...

Страница 28: ...r flow is limited Low pressure pumps options 116T 116U High pressure pumps options 116R 116S Available static pressure kPa Available static pressure kPa Flow rate L s Flow rate L s 0 20 40 60 80 100 1...

Страница 29: ...ity calculations Units with hydronic module enable direct monitoring of flow rate and cooling capacity through IHM refer to 30XAV ZE control manual Fluid pressure is measured by pressure sensors fitte...

Страница 30: ...ns or to complement them follow the guidance programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition of the coating paint to detect blistering resu...

Страница 31: ...id line valve a filter drier two EXVs a plate heat exchanger as well as protection devices seal or valve At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the he...

Страница 32: ...s 6 Nominal input frequency Hz 50 Nominal voltage V 400 Number of phases 3 Motor included in the application domain of the regulation 640 2009 amendment 4 2014 NO Sales leaflet for exemption Article 1...

Страница 33: ...quency drive that allows adjustment the capacity of the compressor by varying the speed of the motor within the frequency range of 27 5 60 Hz Variable speed is produced by generating a controlled volt...

Страница 34: ...water column evaporator side typically high buildings 401 901 Reversed evaporator water connections 107 Evaporator with reversed water inlet outlet Easy installation on sites with specific requirement...

Страница 35: ...901 EMC classification C2 as per EN 61800 3 282 Additional RFI filters on the unit power line Reduces electromagnetic interferences Increase the variable frequency drive VFD immunity level according...

Страница 36: ...ion change Removal or dismantling of the HVAC unit Any intervention due to a missed established mainte nance operation Any intervention covered by the warranty 11 STANDARD MAINTENANCE To ensure optima...

Страница 37: ...t be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals 1 Application torque for tightening the clamp 2 Avoid contact between...

Страница 38: ...ng the pressure at the filter service port and the oil pressure port The difference in these two pressures will be the pressure drop across the filter check valve and solenoid valve The pressure drop...

Страница 39: ...s been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All cables and thermistors have been...

Страница 40: ...il corrective measures have been taken Check evaporator water loop Water loop volume litres Calculated volume litres 3 25 liters nominal kW capacity for air conditioning 6 5 liters nominal kW capacity...

Страница 41: ...he temperatures and pressures have stabilised record the following Evaporator entering water Evaporator leaving water Ambient temperature Circuit A suction pressure Circuit B suction pressure Circuit...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...com www certiflash com Order No 10159 07 2016 Supersedes order No New Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Prin...

Отзывы: