Net positive suction head (NPSH) required, hydraulic module option
Size the hydraulic circuit to ensure a net positive suction head that is higher than or equal to the required NPSH + 50 kPa.
Data applicable for:
-Fresh water 20 °C
-
In case of use of the glycol, the maximum water flow is reduced.
-When the glycol is used, it’s limited to 40%.
Low-pressure pumps (options 116T/116U)