38
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
30XBE from 1100 to 1700
30XBE
1100
1200
1300
1400
1500
1700
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
Standard unit
Circuit 1
(a)
kW
194
223
264
284
307
363
Circuit 2
(a)
kW
284
308
282
305
307
363
Option 081
kW
478
532
546
588
614
-
Unit + option 15LS
Circuit 1
(a)
kW
187
216
255
274
297
351
Circuit 2
(a)
kW
275
298
273
296
297
351
Option 081
kW
461
514
528
570
594
-
Power factor at maximum power
(1)
Standard unit
Displacement Power Factor (Cos Phi)
0,89
0,89
0,89
0,89
0,89
0,90
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,89
0,89
0,89
0,89
0,89
0,90
Nominal operating current draw
(2)
Standard unit
Circuit 1
(a)
A
251
267
334
347
382
439
Circuit 2
(a)
A
350
386
347
379
382
439
Option 081
A
601
652
681
726
764
-
Unit + option 15LS
Circuit 1(
a)
A
239
255
319
332
366
417
Circuit 2
(a)
A
334
367
332
364
366
417
Option 081
A
572
621
650
695
731
-
Maximum operating current draw (Un)
(1)
Standard unit
Circuit 1
(a)
A
316
362
430
460
498
586
Circuit 2
(a)
A
463
500
460
495
498
586
Option 081
A
778
862
889
954
995
-
Unit + option 15LS
Circuit 1
(a)
A
304
350
415
445
482
566
Circuit 2
(a)
A
447
483
445
480
482
566
Option 081
A
751
833
860
925
963
-
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.