33
30XB option 254/255
850
900
1000
1100
1200
1300
1400
1550
1700
Capacity control
SmartVu
TM
, Electronic Expansion Valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
10
8
Air heat exchanger
Aluminum micro-channel coils (MCHE)
Fans
FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity
14
15
16
19
20
20
20
24
28
Maximum total air flow
l/s
67480 72300 77120 91580 96400 96400 96400 115680 134960
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
Unit + option 15LS
Maximum total air flow
l/s
55020 58950 62880 74670 78600 78600 78600 94320 110040
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Water heat exchanger
Flooded multi-pipe type
Water volume
l
119
130
140
164
174
180
189
240
240
Max. water-side operating pressure without hydraulic module
kPa
1000 1000 1000 1000 1000 1000 1000 1000 1000
Water connections
Victaulic
®
type
Standard & option 8
Nominal diameter
in
6
6
8
6
6
6
6
8/6
6
Actual outside diameter
mm
168,3 168,3 219,1 168,3 168,3 168,3 168,3 219,1/
168,3 168,3
Options 5, 6 et 100A
Nominal diameter
in
5
5
6
6
6
6
6
8/5
6/6
Actual outside diameter
mm
141,3 141,3 168,3 168,3 168,3 168,3 168,3 219,1/
141,3
168,3/
168,3
Options 100C
Nominal diameter
in
6
6
8
-
-
-
-
-
-
Actual outside diameter
mm
168,3 168,3 219,1
-
-
-
-
-
-
Casing paint
Colour code RAL 7035
4.5 -
Short-circuit stability current for all units
30XB(E/P)
250 to 500
600 to 1000
1100 to 1500
1550
1700
Short-circuit whistand current (TN system)
Circuit A+B
KA
38
50
50
50
50
Circuit C+D
kA
NA
NA
50
50
50
Unit + option 81
kA
NA
NA
50
50
NA
(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the recommended
protection.
Note: The short-circuit stability current values above are suitable with the TN system.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS