41
30XBP from 1100 to 1500
30XBP
1100
1200
1300
1400
1500
Power circuit supply
Nominal voltage
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1)
- 30XBP
Standard unit
Circuit 1
(a)
kW
191
220
262
282
304
Circuit 2
(a)
kW
279
304
280
303
304
Option 081
kW
469
525
542
584
609
Unit + option 15LS
Circuit 1
(a)
kW
188
217
258
278
301
Circuit 2
(a)
kW
276
301
277
300
301
Option 081
kW
463
518
535
578
602
Power factor at maximum power
(1)
- 30XBP
Standard unit
Displacement Power Factor (Cos Phi)
0,88
0,89
0,88
0,89
0,89
Unit + option 15LS
Displacement Power Factor (Cos Phi)
0,88
0,89
0,88
0,89
0,89
Nominal operating current draw
(2)
- 30XBP
Standard unit
Circuit 1
(a)
A
245
261
330
343
377
Circuit 2
(a)
A
340
377
343
375
377
Option 081
A
584
638
672
717
754
Unit + option 15LS
Circuit 1
(a)
A
240
256
324
337
372
Circuit 2
(a)
A
334
371
337
369
372
Option 081
A
574
627
661
706
743
Maximum operating current draw (Un)
(1)
- 30XBP
Standard unit
Circuit 1
(a)
A
312
358
428
458
495
Circuit 2
(a)
A
455
495
458
493
495
Option 081
A
766
853
885
950
990
Unit + option 15LS
Circuit 1
(a)
A
307
353
422
452
490
Circuit 2
(a)
A
450
490
452
487
490
Option 081
A
756
842
874
939
979
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XBP1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS