![Carrier AquaForce 30XB 1000 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/carrier/aquaforce-30xb-1000/aquaforce-30xb-1000_installation-operation-and-maintenance-instructions_2562362029.webp)
29
30XBP
850
900
1000
1100
1200
1300
1400
1500
Capacity control
SmartVu
TM
, Electronic Expansion Valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
Air heat exchanger
Aluminum micro-channel coils (MCHE)
Fans
FLYING-BIRD 6, axial fan with rotating impeller
Standard unit
Quantity
14
14
16
19
20
20
20
22
Maximum total air flow
l/s
67480
67480
77120
91580
96400
96400
96400 106040
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
Unit + option 15LS
Maximum total air flow
l/s
55020
55020
62880
78600
78600
78600
78600
86460
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Water heat exchanger
Flooded multi-pipe type
Water volume
l
119
130
140
164
174
180
189
189
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air drain valve,
pressure sensors, expansion tank (option)
Pump
Centrifugal pump, monocell, 48,3r/s, low or high pressure (as required),
single or dual (as required)
Expansion vessel volume
inch
Max. water-side operating pressure with hydraulic module
mm
Water connections
Victaulic
®
type
Standard & option 8
Nominal diameter
in
6
6
8
6
6
6
6
6
Actual outside diameter
mm
168,3
168,3
219,1
168,3
168,3
168,3
168,3
168,3
Options 5, 6 et 100A
Nominal diameter
in
5
5
6
6
6
6
6
6
Actual outside diameter
mm
141,3
141,3
168,3
168,3
168,3
168,3
168,3
168,3
Options 100C
Nominal diameter
in
6
6
8
-
-
-
-
-
Actual outside diameter
mm
168,3
168,3
219,1
-
-
-
-
-
Casing paint
Colour code RAL 7035
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS