42
30XBP
1100
1200
1300
1400
1500
Maximum current (Un-10%)
(1)
- 30XBP
Standard unit
Circuit 1
(a)
A
331
380
464
496
526
Circuit 2
(a)
A
493
526
496
524
526
Option 081
A
823
906
959
1019
1052
Unit + option 15LS
Circuit 1
(a)
A
326
375
458
490
521
Circuit 2
(a)
A
488
521
490
518
521
Option 081
813
895
948
1008
1041
Nominal start-up current
(3)
- 30XBP
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
927
964
972
1004
1006
Option 081 & Opt 25c
A
678
691
719
734
733
Unit + option 15LS
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
922
959
966
998
1001
Option 081 & Opt 25c
A
674
685
714
729
727
Maximum start-up current(Un)
(2)
- 30XBP
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
1042
1082
1087
1122
1124
Option 081 & Opt 25c
A
793
809
834
852
851
Unit + option 15LS
Circuit 1
(a)
A
587
587
629
629
629
Circuit 2
(a)
A
629
629
629
629
629
Option 081
A
1037
1077
1081
1116
1119
Option 081 & Opt 25c
A
789
803
829
847
845
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XBP1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS