18
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
4.1 - Physical data 30XB
30XB-250 to 800 standard units
30XB
250
300
350
400
450
500
600
700
750
800
Sound levels
Standard unit
Sound power
(1)
dB(A)
99
99
99
99
101
99
101
99
103
103
Sound pressure at 10 m
(2)
dB(A)
67
67
67
67
69
67
68
67
70
70
Unit + option 15
(3)
Sound power
(1)
dB(A)
93
93
94
95
95
95
97
96
97
98
Sound pressure at 10 m
(2)
dB(A)
61
61
62
63
63
63
65
63
64
65
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
87
87
87
90
91
91
93
92
94
94
Sound pressure at 10 m
(2)
dB(A)
54
54
54
57
58
58
59
58
60
60
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
-
-
-
-
89
89
91
90
91
92
Sound pressure at 10 m
(2)
dB(A)
-
-
-
-
56
56
57
56
58
58
Dimensions
Standard unit
Length
mm
3604 3604 3604 4798 4798 4798 7186 7186 7186 7186
Width
mm
2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height
mm
2322 2322 2322 2322 2322 2322 2322 2322 2322 2322
Operating weight
(4)
Standard unit
kg
2992 3023 3042 3620 3684 3746 4717 4849 5115 5431
Unit + option 15
(3)
kg
3237 3268 3287 3889 3952 4015 5005 5134 5400 5716
Unit + option 118A
(3)
kg
3053 3084 3103 3694 3757 4100 4806 4935 5216 5532
Unit + option 50
(3)
kg
3314 3345 3364 4023 4164 4515 5428 5657 5923 6245
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
37
35
35
51
52
54
58
58
65
69
teqCO
2
52,9
50,1
50,1
72,2
74,4
76,5
82,9
82,9
93,0
98,7
Circuit B
kg
39
36
37
37
37
33
59
62
58
65
teqCO
2
55,1
51,5
52,9
52,2
52,9
46,5
84,4
88,7
82,9
93,0
Oil
Circuit A
l
20,8
20,8
20,8
23,5
23,5
23,5
23,5
23,5
27,6
27,6
Circuit B
l
20,8
20,8
20,8
20,8
20,8
20,8
23,5
23,5
23,5
23,5
(1) In dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified values