17
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XA UNITS
4.1 - Physical data 30XA 252-852
- standard units and units with option 119*
30XA
252
302
352
402
452
504
502
602
702
752
802
854
852
Sound levels - Standard unit
Sound power level***
dB(A)
99
99
99
98
101
-
98
100
98
103
102
-
100
Sound pressure level at 10 m****
dB(A)
67
67
67
65
69
-
65
67
65
70
70
-
67
Standard unit + option 279*
Sound power level***
dB(A)
89
89
89
92
93
-
93
95
94
96
96
-
95
Sound pressure level at 10 m****
dB(A)
57
57
57
60
61
-
61
62
61
63
64
-
63
Standard unit + option 257*
Sound power level***
dB(A)
87
87
87
90
91
-
91
93
92
94
94
-
94
Sound pressure level at 10 m****
dB(A)
55
55
55
58
59
-
59
60
59
61
61
-
61
Standard unit + option 258*
Sound power level***
dB(A)
-
-
-
-
89
-
89
91
90
91
92
-
91
Sound pressure level at 10 m****
dB(A)
-
-
-
-
57
-
56
58
57
59
59
-
59
Standard unit + option 119*
Sound power level***
dB(A)
100
100
100
100
102
100
100
102
100
104
104
102
102
Sound pressure level at 10 m****
dB(A)
68
68
68
68
70
68
68
69
68
71
71
70
69
Standard unit + option 119* + 279*
Sound power level***
dB(A)
94
94
95
96
96
96
96
98
97
98
99
98
98
Sound pressure level at 10 m****
dB(A)
62
62
63
64
64
64
64
66
64
65
66
65
65
Dimensions - standard unit
Length
mm
3604
3604
3604
4798
4798
4798
5992
7186
7186
7186
7186
7186
8380
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
Operating weight**
Standard unit and unit + option 119*
kg
3410
3450
3490
4313
4883
4524
4814
5707
5857
6157
6457
6662
6958
Compressors
06T semi-hermetic screw compressors, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
1
1
1
1
Refrigerant** -Standard unit
R-134a
Circuit A
kg
37
35
35
50.5
52
53.5
58.5
58
58
65
69
69
72
teqCO
2
52.9
50.1
50.1
72.2
74.4
76.5
83.7
82.9
82.9
93.0
98.7
98.7
103.0
Circuit B
kg
38.5
36
37
36.5
37
32.5
36
59
62
58
65
65
63
teqCO
2
55.1
51.5
52.9
52.2
52.9
46.5
51.5
84.4
88.7
82.9
93.0
93.0
90.1
Oil charge
Circuit A
l
20.8
20.8
20.8
23.5
23.5
23.5
23.5
23.5
23.5
27.6
27.6
27.6
27.6
Circuit B
l
20.8
20.8
20.8
20.8
20.8
20.8
20.8
23.5
23.5
23.5
23.5
23.5
23.5
Capacity control
Touch Pilot, electronic expansion valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
15
15
15
15
15
Condensers
All-aluminium microchannel heat exchanger (MCHE)
Fans - Standard unit
Axial Flying Bird IV fans with rotating shroud
Quantity
6
6
6
8
8
-
9
11
12
12
12
-
14
Maximum
total air flow
l/s
20500 20500 20500 27333 27333 -
30750 37583 41000 41000 41000 -
47833
Maximum rotation speed
r/s
11.7
11.7
11.7
11.7
11.7
-
11.7
11.7
11.7
11.7
11.7
-
11.7
Standard unit + option 119*
Quantity
6
6
6
8
8
8
9
11
12
12
12
12
14
Maximum
total air flow
l/s
27083 27083 27083 36111 36111 36111 40625 49653 54167 54167 54167 54167 63194
Maximum rotation speed
r/s
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
Evaporator
Flooded multi-pipe type
Water content
l
58
61
61
66
70
77
77
79
94
98
119
119
119
Without hydronic module
Water inlet/outlet connections
Victaulic
Nominal diameter
in
5
5
5
5
5
5
5
5
6
6
6
6
6
Actual outside diameter
mm
141.3
141.3
141.3
141.3
141.3
141.3
141.3
141.3
168.3
168.3
168.3
168.3
168.3
Maximum water-side pressure
†
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
With hydronic module (option 116)
Water inlet/outlet connections
Victau-
lic
-
Nominal diameter
in
4
4
4
4
4
-
4
-
-
-
-
-
-
Actual outside diameter
mm
114.3
114.3
114.3
114.3
114.3
-
114.3
-
-
-
-
-
-
Expansion tank valume
l
50
50
50
50
50
-
80
-
-
-
-
-
-
Maximum water-side pressure
kPa
400
400
400
400
400
-
400
-
-
-
-
-
-
Chassis paint colour Colour
Colour code: RAL7035
* Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level
** Weights are guidelines only. Refer to the unit nameplate.
*** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1 and certified by Eurovent.
**** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
† Max. water-side operating pressure without hydronic module.
Note: Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
Eurovent certified values