21
4.4 - Electrical data
30XA 252-852 - standard units or units with option 81
30XA
252
302
352
402
452
502
602
702
752
802
852
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
269
269
287
402
505
505
574
606
773
803
805
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
Nominal start-up current***
Circuit 1**
A
245
245
262
378
480
480
536
562
735
759
761
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
Cosine Phi maximum****
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.86
0.86
0.87
Cosine Phi nominal
†
0.85
0.85
0.84
0.84
0.85
0.85
0.85
0.85
0.83
0.84
0.84
Maximum power input
‡
Circuit 1**
kW
121
131
141
165
185
204
247
267
293
312
343
Circuit 2**
kW
-
-
-
-
-
-
-
-
-
-
-
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
Nominal unit current draw
†
Circuit 1**
A
151
167
184
210
242
268
325
352
408
433
453
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
Maximum unit current draw (Un)
‡
Circuit 1**
A
198
215
233
270
303
335
404
436
492
522
572
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
Option 231
A
182
196
211
242
272
305
364
397
448
479
531
Maximum unit current draw
(Un-10%)****
Circuit 1**
A
208
232
251
290
326
360
435
469
529
561
615
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
30XA 902-1702 - standard units or units with option 81
30XA
902
1002
1112
1212
1312
1382
1402
1502
1702
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
893
941
587
587
772
772
893
941
805
Circuit 2**
A
-
-
772
772
772
772
587
587
805
Option 81
A
-
-
1085
1131
1198
1228
1248
1294
-
Nominal start-up current**
Circuit 1**
A
845
865
587
587
772
772
845
865
761
Circuit 2**
A
-
-
772
772
772
772
587
587
761
Option 81
A
-
-
1023
1039
1103
1118
1125
1143
-
Cosine Phi maximum****
0.86
0.87
0.86
0.87
0.87
0.87
0.86
0.87
0.87
Cosine Phi nominal
†
0.85
0.85
0.85
0.86
0.87
0.87
0.86
0.85
0.85
Maximum power input
‡
Circuit 1**
kW
359
420
182
211
256
278
390
420
343
Circuit 2**
kW
-
-
279
302
278
299
210
210
343
Option 81
kW
-
-
460
512
531
571
600
630
-
Nominal unit current draw
†
Circuit 1**
A
508
548
258
274
340
356
530
556
452
Circuit 2**
A
-
-
358
392
356
387
278
278
452
Option 81
A
-
-
616
666
696
743
808
834
-
Maximum unit current draw (Un)
‡
Circuit 1**
A
611
707
313
359
426
456
661
707
572
Circuit 2**
A
-
-
459
496
456
491
354
354
572
Option 81
A
-
-
771
855
882
947
1015
1061
-
Option 231
A
855
662
-
-
-
-
-
-
-
Maximum unit current draw
(Un-10%)****
Circuit 1**
A
657
760
332
381
462
494
711
760
615
Circuit 2**
A
-
-
497
527
494
522
380
380
615
Option 81
A
-
-
828
908
956
1016
1091
1141
-
* Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at operation with maximum unit power input.
** 30XA 1402 to 1702 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D. 30XA 1112, 1212, 1312 and 1382 units: Circuit 1 supplies circuit A,
circuit 2 supplies circuit B.
*** Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
**** Values obtained at operation with maximum unit power input.
† Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
‡ Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Notes:
1. Unit sizes 30XA 1112, 1212, 1312, 1382, 1402 to 1702 have two power connection points.
Содержание Aquaforce 30XA Series
Страница 55: ......