26
4.7 - Electrical data, optional hydronic module
The pumps that are factory-installed in these units have
motors with efficiency class IE2. The additional electrical
data required
*
is as follows:
Motors of single and dual low-pressure pumps for 30XA units (options 116F and116G)
No.** Description***
30XA
252
302
352
402
452
502
1
Nominal efficiency at full load and nominal voltage
%
83.4
83.4
84.8
86.1
88.6
88.6
1
Nominal efficiency at 75% rated load and nominal voltage
%
84
84
85.3
86.3
88.5
88.5
1
Nominal efficiency at 50% rated load and nominal voltage
%
82.9
82.9
84.2
84.7
86.7
86.7
2
Efficiency level
IE2
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
5
Product's model number
6
Number of motor poles
2
7-1
Rated shaft power output at full load and nominal voltage (400 V) kW
2.2
2.2
3
4
5.5
5.5
7-2
Maximum power input (400 V)****
kW
2.6
2.6
3.5
4.6
6.2
6.2
8
Rated input frequency
Hz
50
9-1
Rated voltage
V
3 x 400
9-2
Maximum current drawn at nominal voltage (400 V)
†
A
4.4
4.4
5.8
7.7
10.2
10.2
10
Rated speed
r/s (rpm) 48 (2880)
48 (2880)
48 (2885)
48 (2895)
49 (2935)
49 (2935)
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
††
II - Ambient air temperature
°C
< 40
IV - Maximum air temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres
Non-ATEX environment
Motors of single and dual high-pressure pumps for 30XA units (options 116B and116C)
No.** Description***
30XA
252
302
352
402
452
502
1
Nominal efficiency at full load and nominal voltage
%
86.1
88.6
88.6
90.1
91.3
91.3
1
Nominal efficiency at 75% rated load and nominal voltage
%
86.3
88.5
88.5
89.7
91.4
91.4
1
Nominal efficiency at 50% rated load and nominal voltage
%
84.7
86.7
86.7
87.9
90.3
90.3
2
Efficiency level
IE2
IE2
IE2
IE3
IE3
IE3
3
Year of manufacture
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
5
Product's model number
6
Number of motor poles
2
7-1
Rated shaft power output at full load and nominal voltage (400 V) kW
4.0
5.5
5.5
7.5
11.0
11.0
7-2
Maximum power input (400 V)****
kW
4.6
6.2
6.2
8.3
12.0
12.0
8
Rated input frequency
Hz
50
9-1
Rated voltage
V
3 x 400
9-2
Maximum current drawn at nominal voltage (400 V)
†
A
7.7
10.2
10.2
13.2
18.7
18.7
10
Rated speed
r/s (rpm) 48 (2898)
49 (2935)
49 (2935)
49 - 2935
49 - 2945
49 - 2945
11
Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
††
II - Ambient air temperature
°C
< 40
IV - Maximum air temperature
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the Carrier selection programs.
V - Potentially explosive atmospheres
Non-ATEX environment
* Required by regulation 640/2009 with regard to the application of directive 2005/32/EC on the eco-design requirements for electric motors
** Item number imposed by regulation 640/2009, annex I2b.
*** Description given by regulation 640/2009, annex I2b.
**** To obtain the maximum power input for a unit with hydronic module add the maximum unit power input from the electrical data table to the pump power input.
† To obtain the maximum unit operating current draw for a unit with hydronic module add the maximum unit current draw from the electrical data table to the pump current
draw.
†† Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.