48
Options
No.
Description
Advantages
Use for 30XA
range
CCN to Lon gateway
148D
Two-directional communication board complying with
Lon Talk protocol
Connects the unit by communication bus to a building
management system
252-1702
Bacnet over IP gateway
149
Two-directional high-speed communication using
BACnet protocol over Ethernet network (IP)
Easy and high-speed connection by ethernet line to a
building management system. Allows access to multiple
unit parameters
252-1702
Energy Management
Module
156
Control board with additional inputs/outputs. See
Energy Management Module option chapter
Extended remote control capabilities (set-point reset,
ice storage end, demand limits, boiler on/off
command...)
252-1702
Touch Pilot control, 7"
user interface
158A
Touch Pilot control supplied with a 7 inch colour touch
screen user interface
Enhanced ease of use
252-1702
Leak detection
159
0-10 V signal to report any refrigerant leakage in the
unit directly on the controlller (the leak detector itself
must be supplied by the customer)
Immediate customer notification of refrigerant losses to
the atmosphere, allowing timely corrective actions
252-1702
Dual relief valves
installed w/ 3-way valve
194
Three-way valve upstream of the safety valves on the
evaporator and the oil separator
Valve replacement and inspection facilitated without
refrigerant loss. Comforms to European standard
EN378/BGVD4
252-1382
Compliance with Swiss
regulations
197
Additional tests on the water heat exchangers: supply
(additional of PED documents) supplementary
certificates and test certifications
Conformance with Swiss regulations
252-1702
Compliance with Russian
regulations
199
GOST certification
Conformance with Russian regulations
252-1702
Compliance with
Australian regulations
200
Unit approved to Australian code
Conformance with Australian regulations
252-1702
Power factor correction
231
Capacitors for automatic regulation of power factor (cos
phi) value to 0.95.
Reduction of the real electrical power, compliance with
minimum power factor limit set by utilities
252-1002
Traditional coils (Cu/Al)
254
Coils made of copper tubes with aluminium fins
None
252-1702
(Not available for the
sizes 504, 854, 904)
Traditional coils (Cu/Al)
without slots
255
Coils made of copper tubes with aluminium fins without
slots
None
252-1702
(Not available for the
sizes 504, 854, 904)
Insulation of the evap.
in/out ref.lines
256
Thermal insulation of the evaporator entering/leaving
refrigerant lines with flexible, anti-UV insulant
Prevents condensation on the evaporator entering/
leaving refrigerant lines
252-1702
Low noise level
257
Sound insulation of main noise sources (includes
option 279)
5 to 12 dB(A) quiter than standard unit (depending
model and size). Refer to the physical data table for
detailed values
252-1702
Very low sound level
258
Enhanced sound insulation of main noise sources
combined with fans speed management (includes
option 279)
2 to 3 dB(A) quiter than unit with option 257. Refer to the
physical data table for detailed values
452-1702
(Not available for the
sizes 504, 854, 904)
Enviro-Shield anti-
corrosion protection
262
Coating by conversion process which modifies the
surface of the aluminum producing a coating that is
integral to the coil. Complete immersion in a bath to
ensure 100% coverage. No heat transfer variation,
tested 4000 hours salt spray per ASTM B117
Improved corrosion resistance, recommended for use in
moderately corrosive environments
252-1702
Super Enviro-Shield
anti-corrosion protection
263
Extremely durable and flexible epoxy polymer coating
applied on micro channel heat exchangers by electro
coating process, final UV protective topcoat. Minimal
heat transfer variation, tested 6000 hours constant
neutral salt spray per ASTM B117, superior impact
resistance per ASTM D2794
Improved corrosion resistance, recommended for use in
extremely corrosive environments
252-1702
Welded evaporator water
connection kit
266
Victaulic piping connections with welded joints
Easy installation
252-1702
Compressor enclousure 279
Compressor sound enclosure
4 to 10 dB(A) quiter than standard unit. Refer to the
physical data table for detailed values
252-1702
Evaporator with
aluminium jacket
281
Evaporator covered with an aluminium sheet for
thermal insulation protection
Improved resistance to aggressive climate conditions
252-1702
230 V electrical plug
284
230 V AC power supply source provided with plug
socket and transformer (180 VA, 0.8 Amps)
Permits connection of a laptop or an electrical device
during unit commissioning or servicing
252-1702
Carrier Connect link
(BSS regions only)
298
3G Router board
NOTE 1: Require option 149
NOTE 2: When more than one machine is installed on
site, only one of them shall be equipped with option 298
while all of them must be equipped with option 149
NOTE 3: If the Carrier
®
PlantCTRL™ is on site, option
298 shall be integrated in the Carrier
®
PlantCTRL™
while option 149 is still mandatory for each single unit.
Enabler for Carrier Connect service offer
252-1702
Содержание Aquaforce 30XA Series
Страница 55: ......