33
7.2 - Victaulic water connections
Inlet/outlet diameters without hydronic module
30XA
252
302
352
402
452
504
502
602
702
752
802
854
852
904
Standard
Nominal diameter
in
5
5
5
5
5
5
5
5
6
6
6
6
6
6
Actual outside diameter
mm
141.3
141.3
141.3
141.3
141.3
141.3
141.3
141.3
168.3
168.3
168.3
168.3
168.3
168.3
Options 5, 6 and 100A
Nominal diameter
in
4
4
4
4
4
-
4
5
5
5
5
-
5
-
Actual outside diameter
mm
114.3
114.3
114.3
114.3
114.3
-
114.3
141.3
141.3
141.3
141.3
-
141.3
-
Option 100C*
Nominal diameter
in
5
5
5
5
5
5
5
6
6
6
6
6
6
6
Actual outside diameter
mm
141.3
141.3
141.3
141.3
141.3
141.3
141.3
168.3
168.3
168.3
168.3
168.3
168.3
168.3
30XA
902
1002
1112
1212
1312
1382
1402
1502
1702
Standard
Nominal diameter
in
6
8
6
6
6
6
8/6
8/6
6
Actual outside diameter
mm
168
219
168
168
168
168
219.1/168.3 219.1/168.3 168.3
Options 5, 6 and 100A
Nominal diameter
in
5
6
6
6
6
6
8/5
8/5
6/6
Actual outside diameter
mm
141
168.3
168.3
168.3
168.3
168.3
219.1/141.3 219.1/141.3 168.3/168.3
Option 100C*
Nominal diameter
in
6
8
-
-
-
-
-
-
-
Actual outside diameter
mm
168.3
219.1
-
-
-
-
-
-
-
* Option 100C is not available for sizes 1112 to 1702
Typical water circuit diagram
Installation components
15 Air vent
16 Flexible connection
17 Shut-off valve
18 Charge valve
--- Hydronic module (supplied as an option)
Legend
Components of the unit and hydronic module
A Pressure sensor (A-B = ΔP evaporator)
B Pressure sensor
C Pressure sensor (C-D = ΔP water filter)
D Pressure sensor
1 Victaulic screen filter
2 Expansion tank
3 Relief valve
4 Available pressure pump
5 Drain valve
6 Flow control valve
7 Evaporator
8 Evaporator defrost heater (option)
9 Hydronic module defrost heater (option)
10 Air vent (evaporator)
11 Water drain (evaporator)
12 Expansion compensator (flexible connections)
13 Flow switch
14 Water temperature sensor
1
2
17
16
18
1 2
9
9
9
11
10
12
14
A
5
15
9
9
16
7
8
17
13
B
C
D
6
4
3
Содержание Aquaforce 30XA Series
Страница 55: ......