25
4.5 - Compressor electrical data
Compressor
I Nom*
Std/Option 119
I Max**
(Un)
MHA
LRYA
(Un)
LRDA
(Un)
Cosine
Phi (max.)**
Cosine
Phi (nom.)*
06TSA155
69/64
86
96
170
530
0.90
0.87
06TSA186
87/80
108
120
170
530
0.89
0.86
06TTA266
128/117
158
176
303
945
0.90
0.86
06TTA301
145/132
177
188
388
1210
0.90
0.87
06TTA356
166/153
207
220
388
1210
0.90
0.87
06TUA483
240/225
292
311
587
1828
0.88
0.87
06TUA554
262/241
338
360
587
1828
0.89
0.88
06TVA680
320/302
400
436
772
2315
0.89
0.87
06TVA753
335/315
430
468
772
2315
0.89
0.88
06TVA819
367/347
465
496
772
2315
0.89
0.88
* Average value for the range (unit at Eurovent conditions)
** Value at maximum capacity and nominal voltage (400 V)
Legend
MHA - Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
LRYA
- Locked rotor current for star connection (connection during compressor start-up)
LRDA
- Locked rotor current for delta connection
4.6 - Compressor usage per circuit (A, B, C, D)
Compressor
30XA
252 302 352 402 452 504 502 602 702 752 802 854 852 904 902 1002 1112 1212 1312 1382 1402 1502 1702
06TSA155
AB
B
—
B
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
06TSA186
—
A
AB
—
B
B
B
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
06TTA266
—
—
—
A
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
06TTA301
—
—
—
—
A
—
—
B
—
B
—
—
—
—
—
—
—
—
—
—
—
—
—
06TTA356
—
—
—
—
—
A
A
A
AB
—
B
B
B
—
—
—
—
—
—
—
—
—
BD
06TUA483
—
—
—
—
—
—
—
—
—
A
A
—
—
AB
AB
—
A
—
—
—
B
—
—
06TUA554
—
—
—
—
—
—
—
—
—
—
—
A
A
—
—
AB
—
A
—
—
AC
ABC AC
06TVA680
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
A
—
—
—
—
06TVA753
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
B
—
B
A
—
—
—
06TVA819
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
B
—
B
—
—
—
Electrical data notes and operating conditions for 30XA units:
• 30XA 252-1002 units have a single power connection point; 30XA 1112, 1212,
1312, 1382, 1402 to 1702 units have two connection points.
• The control box includes the following standard features:
-
One general disconnect switch per circuit
-
Starter and motor protection devices for each compressor, the fan(s) and
the pump
-
Control devices
Field connections:
• All connections to the system and the electrical installations must be in full
accordance with all applicable local codes.
• The Carrier 30XA units are designed and built to ensure conformance with
these codes. The recommendations of European standard EN 60204-1
(corresponds to IEC 60204-1) (machine safety - electrical machine compo-
nents - part 1: General regulations) are specifically taken into account, when
designing the electrical equipment.
IMPORTANT:
• Generally the recommendations of IEC 60364 are accepted as compliance
with the requirements of the installation regulations
.
• Conformance with EN 60204 is the best means of ensuring compliance with
the Machines Directive § 1.5.1.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.
1. Environment* - Environment as classified in EN 60364 (corresponds to IEC
60364):
-
Outdoor installation*
-
Ambient temperature range:
from
-20 °C to +55 °C
**
-
Altitude less than or equal to 2000 m (for hydronic module, see
paragraph 4.7 in the IOM)
-
Presence of hard solids, class AE3
* (no significant dust present)
-
Presence of corrosive and polluting substances, class
AF1
(negligible)
-
Competence of persons: BA4 (Persons wise); 30XA machines are not
intended to be installed in locations open to anyone, including people
with disabilities and children.
2. Compatibility for low-frequency conducted disturbances according to
IEC61000-2-2 and to class 2 levels per IEC61000-2-4 standard:
-
Power supply frequency variation : +-2Hz
-
Phase imbalance : 2%
-
Total Voltage Harmonic Distortion (THDV) : 8 %
3. The neutral (N) line must not be connected directly to the unit (if necessary use
a transformer).
4. Overcurrent protection of the power supply conductors is not provided with the
unit.
5. The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947-3 (corresponds to
IEC 60947-3).
6. The units are designed for simplified connection on TN(s) networks (IEC 60364).
For IT networks provide a local earth and consult competent local organisations
to complete the electrical installation. Units delivered with speed drive
(options 28) are not compatible with IT network.
• Derived currents: If protection by monitoring of derived currents is necessary to
ensure the safety of the installation, the control of the cut-out value must take the
presence of leak currents into consideration that result from the use of optional
frequency converters in the unit. In particular, a type of enhanced immunity
protection and/or a value of at least 150 mA is recommended to control
differential protection devices.
• Capacitors that are integrated as part of the option 231 can generate electrical
disturbances in the installation the unit is connected to. Presence of these
capacitors must be considered during the electrical study prior to the start-up.
NOTE: If particular aspects of an actual installation do not conform to
the conditions described above, or if there are other conditions which
should be considered, always contact your local Carrier representative.
* The required protection level for this class is IP43BW (according to reference
document IEC 60529). All 30XA units are protected to IP44CW and fulfil this
protection condition.
**
The maximum ambiant temperature allowed for machines equipped with
option 231 is +40 °C