4.4 - Electrical data (continued)
30XA 252-852 - units with option 119 or units with option 119 and option 81
30XA
252
302
352
402
452
504
502
602
702
752
802
854
852
Power circuit
Nominal power supply
V-ph-Hz 400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
274
274
292
407
510
510
510
583
616
782
812
812
815
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Nominal start-up current***
Circuit 1**
A
246
246
261
379
479
479
479
535
561
734
757
760
760
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Cosine Phi maximum****
0.88
0.87
0.87
0.88
0.88
0.88
0.88
0.88
0.88
0.86
0.86
0.86
0.86
Cosine Phi nominal
†
0.84
0.84
0.83
0.83
0.84
0.84
0.84
0.84
0.84
0.83
0.83
0.83
0.83
Maximum power input
‡
Circuit 1**
kW
126
136
147
172
192
211
212
257
278
304
323
353
356
Circuit 2**
kW
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
-
-
Nominal unit current draw
†
Circuit 1**
A
151
167
182
210
239
267
267
324
349
409
430
446
446
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Maximum unit current draw
‡
Circuit 1**
A
208
226
243
284
316
347
350
423
457
512
542
590
596
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 231
A
192
207
221
256
285
317
320
383
418
468
499
549
555
Maximum unit current draw (Un-10%)****
Circuit 1**
A
219
243
262
305
340
373
376
455
491
551
583
634
640
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
30XA 904-1702 - units with option 119 or units with option 119 and option 81
30XA
904
902
1002
1112
1212
1312
1382
1402
1502
1702
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
902
905
954
587
587
772
772
905
954
815
Circuit 2**
A
-
-
-
772
772
772
772
587
587
815
Option 81
A
-
-
-
1093
1139
1208
1238
1275
1321
-
Nominal start-up current***
Circuit 1**
A
843
845
860
587
587
772
772
845
860
760
Circuit 2**
A
-
-
-
772
772
772
772
587
587
760
Option 81
A
-
-
-
1031
1047
1113
1128
1122
1133
-
Cosine Phi maximum****
0.85
0.85
0.86
0.86
0.87
0.87
0.87
0.86
0.86
0.86
Cosine Phi nominal
†
0.84
0.84
0.84
0.84
0.84
0.85
0.86
0.84
0.84
0.84
Maximum power input
‡
Circuit 1**
kW
369
372
435
186
216
262
284
405
435
356
Circuit 2**
kW
-
-
-
286
309
284
305
217
217
356
Option 81
kW
-
-
-
471
525
544
584
622
652
-
Nominal unit current draw
†
Circuit 1**
A
511
511
541
259
275
341
356
527
546
446
Circuit 2**
A
-
-
-
360
393
356
386
273
273
446
Option 81
A
-
-
-
619
668
697
742
800
820
-
Maximum unit current draw (Un)
‡
Circuit 1**
A
629
635
734
321
367
436
466
688
734
596
Circuit 2**
A
-
-
-
470
508
466
501
367
367
596
Option 81
A
-
-
-
790
875
902
967
1056
1102
-
Option 231
A
582
588
689
-
-
-
-
-
-
-
Maximum unit current draw (Un-10%)****
Circuit 1**
A
677
683
790
340
389
472
504
740
790
640
Circuit 2**
A
-
-
-
508
539
504
532
395
395
640
Option 81
A
-
-
-
847
928
976
1036
1135
1185
-
* Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at operation with maximum unit power input.
** 30XA 1402 to 1702 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D. 30XA 1112, 1212, 1312 and 1382 units: Circuit 1 supplies circuit A,
circuit 2 supplies circuit B.
*** Instantaneous start-up current (operating current of the smallest comp fan c locked rotor current in star connection of the largest compressor). Values
obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
**** Values obtained at operation with maximum unit power input.
† Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
‡ Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Notes:
1. Unit sizes 30XA 1112, 1212, 1312, 1382, 1402 to 1702 have two power connection points.