APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Evap Leaving Water P
LEGEND
Cond Entering Water P
LEGEND
Cond Leaving Water P
LEGEND
Pump Input Press Cali
LEGEND
CCN TABLE NAME: PRSCAL08
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Evap Leaving Water P
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Evap Leaving Water P
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL09
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Cond Entering Water P
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Cond Entering Water P
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL10
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Cond Leaving Water P
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Cond Leaving Water P
2
Calibration Enable
cal_en
DISABLE/ENABLE
DISABLE
RW
3
Calibration Completed
cal_st
NO/YES
NO
RO
4
Calibrated Slope
cal_s
RO
5
Calibrated Intercept
cal_i
RO
6
Current Pressure
cur_pres
psig
RO
7
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (100-250PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write
CCN TABLE NAME: PRSCAL11
PIC6 PATH: Main Menu
Maintenance Menu
Pressure Sensor Calib
Pump Input Press Cali
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
Pump Input Press Cali
cal_en
DISABLE/ENABLE
DISABLE
RW
2
Calibration Completed
cal_st
NO/YES
NO
RO
3
Calibrated Slope
cal_s
RO
4
Calibrated Intercept
cal_i
RO
5
Current Pressure
cur_pres
psig
RO
6
Calib Press1 (0 PSI)
cal_p1
9 digit numeric string
0
psig
RW
8
Calib Press2 (10-30PSI)
cal_p2
9 digit numeric string
0
psig
RW
RO —
Read Only
RW —
Read/Write