72
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Power Load Parameters
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: POWER_O
PIC6 PATH: Main Menu
Maintenance Menu
Power Load Parameters
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
VFD Load Current
VFD_LOAD
amp
RO
2
Percent VFD Load Current
amps_p_o
%
RO
3
Ground Fault Current
gf_amps
amp
RO
4
Motor Current Imbalance
mt_imb_i
%
RO
5
Motor Actual Frequency
MOT_FREQ
Hz
RO
6
Motor Target Frequency
tgt_freq
Hz
RO
7
Actual VFD Speed Per
vfd_act
%
RO
8
DC Bus Voltage
bus_volt
V
RO
9
DC Bus Voltage Reference
bus_ref
V
RO
10
Load Current Ph 1(U)
ld_amps1
amp
RO
11
Load Current Ph 2(V)
ld_amps2
amp
RO
12
Load Current Ph 3(W)
ld_amps3
amp
RO
13
Motor Power Factor
motor_pf
RO
14
Motor Overload
motor_ov
%
RO
15
Motor Kilowatt-Hours
motorkwh
RO
16
Motor Kilowatts
motor_kw
kW
RO
17
Rectifier Overload
rect_ov
%
RO
18
Inverter Overload
inv_ov
%
RO
19
Motor Overload Factor
ov_fact
RO
20
VFD Enclosure Temp
enc_temp
°F
RO
21
VFD Cold Plate Temp
cp_temp
°F
RO
22
Inverter Temperature
inv_temp
°F
RO
23
Rectifier Temperature
rec_temp
°F
RO
24
Shunt Trip Relay Status
tripr
0 to 1
RO
25
Precharge Relay Status
prechar
0 to 1
RO
26
VFD Run Relay Status
vfd_run
0 to 1
RO
27
Precharge Feedback
prech_fd
0 to 1
RO
28
VFD Load Factor
VFD_FACT
RO
29
LR Temp Switch
lrtem_sw
0 to 1
RO
30
VFD Alarm Code
alm_code
RO
31
VFD Status Word
stat_wd
RO
32
VFD Command Word
cmd_wd
RO
33
VFD Start Inhibit Status
str_inh
RO
34
VFD Appl Digital Output
appl_do
RO
35
Safety Stop Status
safestop
0 to 1
RO
36
SPD Feedback
spd_fd
0 to 1
RO
37
High VFD Current
VFDC_HI
NO/YES
RO
RO —
Read Only