4
Table 4 — 19DV IOB3 Connections
NOTES:
1.
See Fig. 3 for IOB3 wiring diagram.
2.
For pressure readings, only Vout (output) terminal is indicated. See Fig. 3 for
Vin (+) and ground (–).
3.
Defaults are shown. In some cases the IOB can be configured differently
depending on job requirements.
Table 5 — 19DV IOB4 Connections
NOTES:
1.
See Fig. 4 for IOB4 wiring diagram.
2.
For pressure readings, only Vout (output) terminal is indicated. See Fig. 4 for
Vin (+) and ground (–).
3.
Defaults are shown. In some cases the IOB can be configured differently
depending on job requirements.
Table 6 — SIOB Input/Output Descriptions
DESCRIPTION
CHANNEL
TERMINAL
TYPE
OPTIONAL
1st Stage Bearing Temperature
AI1
J16-1,5
5 k
—
2nd Stage Bearing Temperature
AI2
J16-2,6
5 k
—
Guide Vane 2 Actual Position
AI4
J16-4,8
4 to 20 mA
—
Remote Reset Temperature
AI5
J15-6,12 (5TB-27,28)
5 k
Yes
Guide Vane 1 Actual Position
AI6
J15-5,11
4 to 20 mA
—
Common Chilled Water Supply (CHWS) Temperature
AI7
J15-4, 10 (5TB,29,30)
5 k
Yes
Auto Water Temperature Reset
AI8
J15-3,9 (5TB-31,32)
4 to 20 mA
Yes
Common Chilled Water Return (CHWR) Temperature
AI9
J15-2, 8 (5TB-37,38)
5 k
Yes
Head Pressure Output
AO1
J14-1,4
4 to 20 mA
Yes
Head Pressure Output2
AO2
HDPV_OU2
4 to 20 mA
Yes
Guide Vane 2 Output
AO3
J14-3, 6 (5TB-5,6)
4 to 20 mA
No
Spare Safety
DI3
J13,7 (5TB-19,20)
24 VAC
Yes, NO (dry contact)
Chilled Water Pump
DO3
J12-2 (5TB-5,6)
24 VAC
Yes
Condenser Water Pump
DO4
J12-5 (5TB-7,8)
24 VAC
Yes
LEGEND
IOB
—
Input/Output Board
NO
—
Normally Open
DESCRIPTION
CHANNEL
TERMINAL
TYPE
OPTIONAL
Entering Evaporator Water Temperature /
Chilled Water Delta P
AI3
J16-7(5TB51, 52)
5 VDC
Yes
Leaving Evaporator Water Pressure /
Condenser Water Delta P
AI4
J16-8(5TB-48, 49)
5 VDC
Yes
Entering Condenser Water Pressure
AI5
J15-6(5TB-45, 46)
5 VDC
Yes
Leaving Condenser Water Pressure
AI6
J15-5(5TB-42, 43)
5 VDC
Yes
Evaporator Water Flow Measurement
AI8
J15-3, 9(5TB-53, 54)
4 to 20 mA
Yes
Condenser Water Flow Measurement
AI9
J15-2, 8(5TB-55, 56)
4 to 20 mA
Yes
Chilled Water Pump (Variable)
AO1
J14-1, 4 (5TB-57, 58)
4 to 20 mA
—
Condenser Water Pump (Variable)
AO2
J14-2, 5 (5TB-59, 60)
4 to 20 mA
—
Tower Fan (Variable)
AO3
J14-3, 6 (5TB-61, 62)
4 to 20 mA
—
Customer Alert
DI3
J13-3, 7 (5TB-63,64)
24 VAC
Yes, NO (dry contact)
Free Cooling Start Switch
DI4
J13-4, 8 (5TB-65,66)
24 VAC
Yes, NO (dry contact)
Free Cooling Mode
DO1
J12-7 (5TB-67)
24 VAC
—
Power Request Output
DO2
J12-10 (5TB-68)
24 VAC
—
Tower Fan High
DO3
J12-2 (5TB-69)
24 VAC
Yes
Tower Fan Low
DO4
J12-5 (5TB-70)
24 VAC
Yes
LEGEND
IOB —
Input/Output Board
NO
—
Normally Open
DESCRIPTION
CHANNEL
TERMINAL
TYPE
OPTIONAL
Purge Compressor Inlet Temperature
AI1
J25-1,2
5 k
—
Low Level Switch Relay
DI1
J1-1, 2
24 VAC
—
High Level Switch Relay
DI2
J1-3, 4
24 VAC
—
Purge Condenser Valve
DO1
J2-2
24 VAC
—
Purge Compressor Valve
DO2
J2-1
24 VAC
—
Purge Pumpout Valve
DO3
J6-2
24 VAC
—
Purge Drainage Valve
DO4
J6-1
24 VAC
—
Purge Regeneration Valve
DO5
J23-2
24 VAC
—
Purge Discharge Valve
DO6
J22-2
24 VAC
—
Purge Vacuum Pump Relay
DO7
J7-7, 8
24 VAC
—
Purge Compressor Contactor
DO8
J7-5, 6
24 VAC
—
Purge Control Valve
DO9
J7-2,4
24 VAC
—
Purge Heater Contactor
DO10
J7-1, 2
24 VAC
—