APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Factory Parameters
Service Parameters
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: FACTORY
PIC6 PATH: Main Menu
Configuration Menu
Factory Parameters
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Chiller Type
0=19XR6/7, 1=19XR2-5/E/D/V, 2=19DV,
3=19XRF
chil_typ
0 to 2
0
RW
2
VFD/Starter Option
0 = Starter with ISM, 1 = FS VFD with ISM,
2=Carrier 32VS VFD, 3=Rockwell LF2 VFD,
4=EATON VFD, 5=Rockwell Std Tier VFD,
7= Danfoss VFD, 8 = Benshaw Starter
vfd_opt
0 to 5
0
RW
3
Unit Type
0 = Cool Only, 1 = Heat Machine
unit_typ
0 to 1
0
RW
4
Chilled Medium Type
chmedium
WATER/BRINE
WATER
RW
5
19DV Design Pressure
0=44 psi, 1=72 psi
comp_pre
0 to 1
0
RW
6
Country Code
coun_cod
0 to 500
86
RW
7
Free Cooling Option
freecool
YES/NO
NO
RW
8
IOB3 Option (19XR2-E/D/V)
YES/NO
YES
RW
9
IOB4 Option
hyd_opt
YES/NO
NO
RW
10
Guide Vane1 Type
0 = Digital, 1 = Analog
gv1_type
0 to 1
0
RW
11
Marine Option
mrn_opt
DISABLE/ENABLE
DISABLE
RW
12
Marine Transducer
mm_pt
DISABLE/ENABLE
DISABLE
RW
13
Power Request Option
pr_opt
DISABLE/ENABLE
DISABLE
RW
14
Cont. Power Request
cpr_opt
DISABLE/ENABLE
DISABLE
RW
CCN TABLE NAME: SERVICE1
PIC6 PATH: Main Menu
Configuration Menu
Service Parameters
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Service Password
ser_pass
0 to 65535
2222
RW
2
Atmospheric Pressure
atom_pre
8 to 15
14.5
psi
RW
3
GV1 Travel Limit
gv1_lim
30 to 100
80
%
RW
4
GV1 Closure at Startup
gv1stpos
0 to 40
4
%
RW
5
Maximum GV Movement
max_gv
2.0 to 4.0
2.0
%
RW
6
Controlled Fluid DB
ctrl_db
0.5 to 2.0
1.0
°F
RW
7
Derivative EWT Gain
ewtdgain
1.0 to 3.0
2.0
RW
8
Proportional Dec Band
gv1decdb
2.0 to 10.0
6.0
RW
9
Proportional Inc Band
gv1incdb
2.0 to 10.0
6.5
RW
10
Demand Limit At 20 mA
dem_20ma
10 to 100
40
%
RW
11
Demand Limit Prop Band
dem_pdb
3.0 to 15.0
10.0
%
RW
12
Amps or KW Ramp per Min
ldramprt
5 to 20
10
%
RW
13
Temp Ramp Rate per Min
tmramprt
1 to 10
3
°F
RW
14
Recycle Shutdown Delta T
rcysh_dt
0.5 to 4.0
1.0
°F
RW
15
Recycle Restart Delta T
rcyst_dt
2.0 to 10.0
5.0
°F
RW
16
Lub Press Verify Time
oilpvr_t
15 to 300
180
s
RW
17
Water Flow Verify Time
wflow_t
0.5 to 5.0
5.0
min
RW
18
Soft Stop Amps Threshold
st_st_th
40 to 100
70
%
RW
19
Power Calibration Factor
mbb_pfcl
0.5 to 2.0
1.0
RW
20
Enable Excessive Starts
ex_start
No/Yes
No
RW
RW —
Read/Write