61
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Temperature Reset
LEGEND
*Default value is shown only if configurable in this table.
Schedule Menu
Navigation: MAIN MENU
CONFIGURATION MENU
SCHEDULE MENU
Fig. B — Schedule Menu and Submenus
CCN TABLE NAME: RESETCFG
PIC6 PATH: Main Menu
Configuration Menu
Temperature Reset
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Temp Reset Type
0 = No, 1 = 4 to 20 mA
2 = Remote Temp, 3 = Water DT [delta tem-
perature]
res_sel
0 to 3
0
RW
2
Degrees Reset At 20 mA
der_20ma
–30.0 to 30.0
10.0
°F
RW
3
Maximum Deg Temp Reset
deg_rset
–30.0 to 30.0
10.0
°F
RW
4
Remote Temp Full Reset
remtm_fu
–40.0 to 245.0
65.0
°F
RW
5
Remote Temp No Reset
remtm_no
–40.0 to 245.0
85.0
°F
RW
6
Deg Reset Water DT Full
drwdt_fu
–30.0 to 30.0
10.0
°F
RW
7
Controlled DT Full Reset
ctldt_fu
0.0 to 15.0
0.0
°F
RW
8
Controlled DT No Reset
ctldt_no
0.0 to 15.0
10.0
°F
RW
RW —
Read/Write
ICON
DISPLAYED TEXT
ACCESS
ASSOCIATED TABLE
Local Schedule
User
Ice Build Schedule
User
Network Schedule
User