ALT-166
Process Alert –
Condenser
Flushing
Automatic
Alert Relay is ON
Flush condenser
ALT-167
Process Alert –
Customer Alert
Automatic
Alert Relay is ON
Check Customer Alert input contact
ALT-169
Process Alert -
High Evaporator
Pressure
Automatic
Alert Relay is ON
Check evaporator pressure sensor input and check evaporator pressure
override configurations
ALT-170
Master Slave
Alert - Master
Slave Same
Address
Manual
Master slave work
independent
Check master slave address configurations
ALT-171
Master Slave
Alert - Conflict
SW Version
Manual
Master slave work
independent
Check master slave SW version number
ALT-172
Master Slave
Alert - Conflict
Cooling Heating
Mode
Manual
Master slave work
independent
Check master slave cooling heating selection
ALT-173
Master Slave
Alert - Incorrect
Slave Control
Type
Manual
Master slave work
independent
Check slave control type
ALT-174
Master Slave
Alert - Slave
Tripout
Manual.
automatic in
Master side
Master slave work
independent
Check slave chiller alarms
ALT-175
Master Slave
Alert - Incorrect
Master Control
Type
Manual
Master slave work
independent
Check master control type
ALT-176
Master Slave
Alert - No
Communication
Master / Slave
Automatic
Master slave work
independent
Check communication between master and slave, wiring, etc.
ALT-179
Master Slave
Alert - Master
CCN Write
Rejection
Manual
Master slave work
independent
Check CCN communication, hardware and software
ALT-180
Master Slave
Alert - Slave
address not slave
Manual
Alert Relay is ON
Check master slave configurations
ALT-181
Loss
Communication
with AHF GDCB 1
Manual
Alert Relay is ON
Check the communication configurations between the main control
board and GDCB1 board, and the cables, etc.
ALT-182
Loss
Communication
with AHF GDCB 2
Manual
Alert Relay is ON
Check the communication configurations between the main control
board and GDCB2 board, and the cables, etc.
ALT-183
Loss
Communication
with AHF GDCB 3
Manual
Alert Relay is ON
Check the communication configurations between the main control
board and GDCB3 board, and the cables, etc.
ALT-184
Loss
Communication
with AHF GDCB 4
Manual
Alert Relay is ON
Check the communication configurations between the main control
board and GDCB4 board, and the cables, etc.
ALT-185
AHF GDCB 1
Start Failure
Manual
Alert Relay is ON
Check AHF GDCB board 1 and the related configurations
ALT-186
AHF GDCB 2
Start Failure
Manual
Alert Relay is ON
Check AHF GDCB board 2 and the related configurations
ALT-187
AHF GDCB 3
Start Failure
Manual
Alert Relay is ON
Check AHF GDCB board 3 and the related configurations
ALT-188
AHF GDCB 4
Start Failure
Manual
Alert Relay is ON
Check AHF GDCB board 4 and the related configurations
Table 15 — PIC6 Alert Codes* (cont)
ALERT CODE
DESCRIPTION
OF ALARM TEXT
RESET TYPE
ACTION TAKEN BY
THE CONTROL
POSSIBLE CAUSE