55
6.3.7.1. Freeze Limits
This setting controls the temperature level to which the loop liquid can drop before
the Geo HP unit will stop operating. See the Geo HP Installation Instructions for
more details. Typically, 26
_
F is chosen for open--loop systems using untreated
water; and 15
_
F is chosen for closed--loop systems using glycol or other anti--freeze
solutions. After the selection is made, touch
SAVE
.
S
Freeze Limits:
26
_
F or 15
_
F
d
Default = 26
_
F
A150179
Содержание A180218C
Страница 2: ...US Patents Carrierr U S Pat No 7 243 004 Carrierr U S Pat No 7 775 452 pointSETt U S Pat No 7 415 102...
Страница 64: ...54 A160188C...
Страница 112: ...102 A160170 NIM Chart...
Страница 113: ...103 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 114: ...104 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 115: ...105 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 116: ...106 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 119: ...109 NOTES...