61
With this option, the installer has the option of selecting pressure monitoring, the
type of filter installed, and the time interval for cleaning. After the selections are
made, touch
SAVE
.
S
Pressure Monitoring
(not available or effective with air cleaners that do not
use filter media, such as Electric Air Cleaners): Enable or Disable
d
Default = Enable
S
Clean Interval:
Selectable from 1 to 18 months
d
Default = 3 months
S
Filter Type:
Air Filter, Electric Air Cleaner or Air Purifier
d
Filter type is selected during installation; otherwise default = air filter
6.3.9.2.
Humidifier
With this option, the installer has the option of selecting whether a humidifier is
installed, to humidify with the fan in low speed, and the time interval for changing
the humidifier pad. After the selections are made, touch
SAVE
.
S
Humidifier Installed:
Yes or No
d
Humidifier selection made during installation; otherwise default = no
S
Change Pad:
Selectable from 1 to 24 months
d
Default = 12 months
S
Humidify with Fan:
Yes or No
d
Default = No
6.3.9.3.
Ultraviolet Lights
With this option, the installer has the option of selecting whether ultraviolet lights
are installed, and the time interval for changing the ultraviolet lights. After the
selections are made, touch
SAVE
.
S
UV Lights Installed:
Yes or No
d
UV Lights selection made during installation; otherwise default = no
Содержание A180218C
Страница 2: ...US Patents Carrierr U S Pat No 7 243 004 Carrierr U S Pat No 7 775 452 pointSETt U S Pat No 7 415 102...
Страница 64: ...54 A160188C...
Страница 112: ...102 A160170 NIM Chart...
Страница 113: ...103 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 114: ...104 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 115: ...105 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 116: ...106 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 119: ...109 NOTES...