10
NOTE
: ABCD bus wiring only requires a four--wire connection; however, it is
good practice to run thermostat cable having more than four wires in the event of a
damaged or broken wire during installation.
Each communicating device in the Infinity Zone System has a four--pin connector
labeled ABCD. It is recommended that the following color code be used when
wiring each device:
A — Green = Data A+
B — Yellow = Data B--
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
A B C D
A03193
It is not mandatory that the above color code be used, but each ABCD connector in
the system MUST be wired consistently.
NOTE
: Some outdoor units, typically those with multiple compressor stages,
provide their own low--voltage power source and do not require the “C” (24VAC
common) and “D” (24VAC power) connections. See the outdoor unit installation
instructions for more information.
Содержание A180218C
Страница 2: ...US Patents Carrierr U S Pat No 7 243 004 Carrierr U S Pat No 7 775 452 pointSETt U S Pat No 7 415 102...
Страница 64: ...54 A160188C...
Страница 112: ...102 A160170 NIM Chart...
Страница 113: ...103 A160171 Wiring Diagram Single Stage Non Communicating Heat Pump NIM...
Страница 114: ...104 A160172 Wiring Diagram Two Stage Non Communicating Heat Pump NIM...
Страница 115: ...105 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation...
Страница 116: ...106 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown...
Страница 119: ...109 NOTES...