T-316
5–2
1. Make sure that the start-stop switch (ST, on control panel) and circuit breakers CB-1 (in the control box and
CB-2 (on the transformer) are in position “0” (OFF). Plug in and lock the 460 vac power plug at the recepta-
cle on the transformer.
2. Plug the 230 vac (black) cable into a de-energized 190/230 vac, 3-phase power source. Energize the power
source. Set circuit breakers CB-1 and CB2 to position “I” (ON). Close and secure control box door.
Figure 5.1 Autotransformer
5.3
ADJUST FRESH AIR MAKEUP VENT
The purpose of the fresh air makeup vent is to provide ventilation for commodities that require fresh air circulation.
The vent
must be closed
when transporting frozen foods.
Air exchange depends on static pressure differential, which will vary depending on the container and how the con-
tainer is loaded.
Units may be equipped with a Vent Position Sensor (VPS). The VPS determines the position of the fresh air vent
(upper or lower, as equipped) and sends data to the controller display.
5.3.1
Upper Fresh Air Makeup Vent
Two slots and a stop are designed into the disc for air flow adjustments. The first slot allows for a 0 to 30% air flow,
and the second slot allows for a 30 to 100% air flow. To adjust the percentage of air flow, loosen the wing nut and
rotate the disc until the desired percentage of air flow matches with the arrow. Tighten the wing nut. To clear the
gap between the slots, loosen the wing nut until the disc clears the stop.
gives air exchange values for
an empty container. Higher values can be expected for a fully loaded container.
460VAC Power Receptacle
Circuit Breaker (CB-2) 230V
Dual Voltage Modular Autotransformer
Содержание 69NT40-541-001
Страница 2: ......
Страница 4: ......
Страница 10: ...T 316 vi...
Страница 14: ......
Страница 20: ......
Страница 24: ......
Страница 36: ......
Страница 79: ...5 9 T 316 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode...
Страница 138: ......
Страница 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Страница 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 144: ...T 316 8 6 Figure 8 5 SCHEMATIC DIAGRAM Emergency Bypass To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER...
Страница 150: ......
Страница 154: ......
Страница 155: ......