3–9
T-316
3.4
SAFETY AND PROTECTIVE DEVICES
Unit components are protected from damage by safety and protective devices listed in the following table. These
devices monitor the unit operating conditions and open a set of electrical contacts when an unsafe condition
occurs.
Open safety switch contacts on either or both of devices IP-CP or HPS will shut down the compressor.
Open safety switch contacts on device IP-CM will shut down the condenser fan motor.
The entire refrigeration unit will shut down if one of the following safety devices open: (a) Circuit Breaker(s), (b)
Fuse (F3A&F3B/7.5A), or (c) Evaporator Fan Motor Internal Protector(s) - (IP-EM).
g. Fuses
Control Circuit
7.5 amps (F3A, F3B)
Controller/DataCORDER
5 amps (F1 & F2)
Emergency Defrost
5 amps (FED)
Drain Line Heater
5 amps (FDH)
Humidity Power
Transformer
5 amps (FH)
h. Compressor Crankcase Heater
180 watts @ 460 vac
i. Humidity Sensor
Orange wire
Power
Red wire
Output
Brown wire
Ground
Input voltage
5 vdc
Output voltage
0 to 3.3 vdc
Output voltage readings verses relative humidity (RH) percentage:
30%
0.99 V
50%
1.65 V
70%
2.31 V
90%
2.97 V
j. Controller
Setpoint Range
-30 to +30°C (-22 to +86°F)
Table 3–1 Safety and Protective Devices
UNSAFE CONDITION
SAFETY DEVICE
DEVICE SETTING
Excessive current draw
Circuit Breaker (CB-1) - Manual Reset
Trips at 29 amps (460 vac)
Circuit Breaker (CB-2, 50 amp) -Manual Reset
Trips at 62.5 amps (230 vac)
Circuit Breaker (CB-2, 70 amp) -Manual Reset
Trips at 87.5 amps (230 vac)
Excessive current draw
in the control circuit
Fuse (F3A & F3B)
7.5 amp rating
Excessive current draw
by the controller
Fuse (F1 & F2)
5 amp rating
Excessive current draw by
the emergency defrost circuit
Fuse (FED)
5 amp rating
Excessive condenser fan
motor winding temperature
Internal Protector (IP-CM) - Automatic Reset
N/A
Excessive compressor motor
winding temperature
Internal Protector (IP-CP) - Automatic Reset
N/A
3.3
ELECTRICAL DATA (CONTINUED)
Содержание 69NT40-541-001
Страница 2: ......
Страница 4: ......
Страница 10: ...T 316 vi...
Страница 14: ......
Страница 20: ......
Страница 24: ......
Страница 36: ......
Страница 79: ...5 9 T 316 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode...
Страница 138: ......
Страница 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Страница 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 144: ...T 316 8 6 Figure 8 5 SCHEMATIC DIAGRAM Emergency Bypass To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER...
Страница 150: ......
Страница 154: ......
Страница 155: ......