T-316
4–28
P5-0
Supply/Return Probe Test
Setup:
The High Speed Evaporator Fan is turned on and run for eight
minutes, with all other outputs de-energized.
Pass/Fail Criteria:
A temperature comparison is made between the re-
turn and supply probes.
If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe tests (this
test and the PRIMARY/ SECONDARY) pass, the display will read “P5”
“PASS.”
P5-1
Supply Probe Test
Requirements:
For units equipped with secondary supply probe only.
Pass/Fail Criteria: The temperature difference between primary and sec-
ondary probe (supply) is compared.
NOTE
If this test fails, “P5-1” and FAIL will be displayed. If both Probe
tests (this and the SUPPLY/ RETURN TEST) pass, because of
the multiple tests, the display will read 'P 5' 'PASS'.
P5-2
Return Probe Test
Requirements:
For units equipped with secondary return probe only.
Pass/Fail Criteria:
The temperature difference between primary and sec-
ondary probe (return) is compared.
NOTES
1. If this test fails, “P5-2” and “FAIL” will be displayed. If both Probe
tests (this test and the SUPPLY/ RETURN) pass, because of the
multiple tests, the display will read “P 5,” “PASS.”
2. The results of Pre-Trip tests 5-0, 5-1, and 5-2 will be used to acti-
vate or clear control probe alarms.
P-6
Not Applicable
P6-0
Compressor On
Setup:
A current draw test is performed before the compressor is started.
The compressor is started. SMV is opened and another current draw test
is per formed.
Pass/Fail Criteria: P
asses if the change in compressor current draw is
within the specified range.
P6-H & P6L
Not Applicable
P6-2
Suction Modulation Valve
(Open and Closed)
Setup:
The compressor and fans continue to run from the previous test.
The quench valve (if configured) will operate as in normal control mode.
The SMV is closed to 0% open, current and condenser pressure readings
are taken. The SMV is opened to 50% with continuous current and con-
denser pressure readings taken to establish maximum values. The SMV
is returned to 0% open and final readings are taken.
Pass/Fail Criteria:
Passes if the calculated difference in current at the
50% open position are above a specified value before and after opening
of the SMV, OR the calculated difference in condenser pressure at the
50% open position are above a specified value before and after opening
of the SMV
P6-3
Quench Valve Test
Setup:
The compressor suction temperature is measured with the
Quench valve closed. The Quench valve is energized and the suction
temperature drop is checked.
Pass/Fail Criteria:
Passes if suction temperature is within the valid range.
P6-4
Not Applicable
Not Used
Table 4–7 Controller Pre-Trip Test Codes (Continued)
CODE #
TITLE
DESCRIPTION
Содержание 69NT40-541-001
Страница 2: ......
Страница 4: ......
Страница 10: ...T 316 vi...
Страница 14: ......
Страница 20: ......
Страница 24: ......
Страница 36: ......
Страница 79: ...5 9 T 316 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode...
Страница 138: ......
Страница 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Страница 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 144: ...T 316 8 6 Figure 8 5 SCHEMATIC DIAGRAM Emergency Bypass To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER...
Страница 150: ......
Страница 154: ......
Страница 155: ......