Figure 7.17 Water-Cooled Condenser Cleaning - Forced Circulation
5. Allow the Oakite No. 32 solution to soak in the tube coils for several hours, periodically pump-circulating
it with an acid-proof pump.
An alternate method may be used whereby a pail (see
) filled with the solution and attached
to the coils by a hose can serve the same purpose by filling and draining. The solution must contact the
scale at every point for thorough de-scaling. Air pockets in the solution should be avoided by regularly
opening the vent to release gas.
Keep flames away from the vent gases
.
Figure 7.18 Water-cooled Condenser Cleaning - Gravity Circulation
6. The time required for de-scaling will vary, depending upon the extent of the deposits. One way to determine
when de-scaling has been completed is to titrate the solution periodically, using titrating equipment provided
free by the Oakite Technical Service representative. As scale is being dissolved, titrate readings will indicate
that the Oakite No. 32 solution is losing strength. When the reading remains constant for a reasonable time,
this is an indication that scale has been dissolved.
7. When de-scaling is complete, drain the solution and flush thoroughly with water.
Centrifugal pump
30 GPM at 35’ head
Pump
Suction
Pump
support
Tank
Fine mesh
screen
Return
Remove water
regulating valve
Condenser
Globe
valves
Vent
Close vent pipe
valve when pump
is running.
Priming
connection
Fill condenser with clean-
ing solution. Do not add
solution more rapidly than
vent can exhaust gases
caused by chemical
action.
Condenser
Vent
pipe
1” Pipe
5’ Approximate
3’ to 4’
Содержание 69NT40-541-001
Страница 2: ......
Страница 4: ......
Страница 10: ...T 316 vi...
Страница 14: ......
Страница 20: ......
Страница 24: ......
Страница 36: ......
Страница 79: ...5 9 T 316 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode...
Страница 138: ......
Страница 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Страница 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 144: ...T 316 8 6 Figure 8 5 SCHEMATIC DIAGRAM Emergency Bypass To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER...
Страница 150: ......
Страница 154: ......
Страница 155: ......