45
G
J4-12
J4-10
J4-8
Y1
Y2
2
R
R
4
6
J4-6
J4-4
W2
C
8
10
C
SPACE
THERMOSTAT
PL
CTB
THERMOSTAT
W1
TB1
CTB
THERMOSTAT
C08119
Fig. 55 -- Space Thermostat Connections
If the 50TCQ unit has an economizer system and
free--cooling operation is required, a sensor representing
Return Air Temperature must also be connected
(field--supplied and installed). This sensor may be a T--55
Space Sensor (see Fig. 51) installed in the space or in the
return duct, or it may be sensor P/N 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB1--1
and TB1--3 per Fig. 52.
Configure the Unit for Thermostat Mode —
Connect to the CCN bus using a CCN service tool and
navigate to PremierLink
t
Configuration screen for
Operating Mode. Default setting is Sensor Mode (value 1).
Change the value to 0 to reconfigure the controller for
Thermostat Mode.
When the PremierLink controller is configured for
Thermostat Mode, these functions are not available: Fire
Shutdown
(FSD),
Remote
Occupied
(RMTOCC),
Compressor Safety (CMPSAFE), Supply Fan Status
(SFS), and Filter Pressure Switch (FILTER).
Table 22 – PremierLink Controller Sensor Usage
APPLICATION
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
Differential Dry Bulb
Temperature with
PremierLink
(PremierLink requires
4---20 mA Actuator)
Included ---
CRTEMPSN001A00
Required ---
33ZCT55SPT
or equivalent
---
---
Single Enthalpy with
PremierLink
(PremierLink requires
4---20mA Actuator)
Included ---
Not Used
---
Requires ---
33CSENTHSW
---
Differential Enthalpy
with PremierLink
(PremierLink requires
4---20mA Actuator)
Included ---
Not Used
---
Requires ---
33CSENTHSW
or equivalent
Requires ---
33CSENTSEN
or equivalent
NOTES
:
CO
2
Sensors (Optional):
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO
2
room sensor.
33ZCT55CO2 --- Space temperature and CO
2
room sensor with override.
33ZCT56CO2 --- Space temperature and CO
2
room sensor with override and setpoint.
Содержание 50TCQD
Страница 5: ...5 C14192 Fig 2 Unit Dimensional Drawing 14 Size Unit ...
Страница 6: ...6 C14193 Fig 2 Unit Dimensional Drawing 14 Size Unit cont ...
Страница 10: ...10 C10365 Fig 6 Roof Curb Details ...
Страница 17: ...17 a50 9707 Fig 26 Typical 50TCQ Control Wiring Diagram ...
Страница 18: ...18 a50 9708 Fig 27 Typical 50TCQ Power Wiring Diagram 208 230V 3 Phase 60Hz unit shown ...
Страница 43: ...43 a50 9710 Fig 50 PremierLinkt Controller Wiring Schematic ...
Страница 51: ...51 a50 9711 Fig 66 RTU Open Controller System Wiring Diagram ...